For clarity in the examples, relay responses are printed in the Courier typeface.

EXIT command example: exit after making setting changes.

EXIT
>SAVE CHANGES (Y/N/C)?

Prompt to save (Y)es, discard changes (N)o, or (C)ontinue

>Y

Confirmation to save changes

CHANGES SAVED

Confirmation that changes were saved

Obtaining Help Information Through the Serial Port

The HELP or H command provides general help information on command syntax and functionality when
the manual is not available. Help is available only when the relay is in a reset state.

HELP Command

Purpose:

Obtains help on using serial port commands.

Syntax:

HELP or H

Comments:

The HELP command returns a listing of all available commands along with the proper

syntax for each command.

Obtaining a Summary of All Settings

All relay settings may be listed using the S command.

S Command

Purpose:

Read all relay settings back to user.

Syntax:

SP-79A[n]

Comments: S by itself may be used to read all relay settings. SP-79A[n] is used to read a specific

setting. the S command can be used to make a record of the relay settings after they have
been set.

S command example: Obtain a report of the relay settings.

A=
S
SP-79A1 5,10
SP-79A2 15,20
SP-79A3 25,30
SP-79A4 35,40
SP-79ALO 45,50
SP-79ARS D,0,5
SP-ALM 2
>

Reclose and Reset Timer Setting Command

SP-79A Command

Purpose:

Read or change the reclose and reset timer settings.

Syntax:

S[-79a[n][=,]

Comments:

n: reclose number of LO for lockout. See Table 4-1 for setting defaults.

reclose time delay: adjustable from 0 to 300 seconds in 0.1 second steps. A Reclose 1
setting of zero will cause an instantaneous first reclosure. A setting of zero for any other
reclose time delay disables the reclose shot and subsequent shots.

reset time delay: adjustable from 0 to 300 seconds in 0.1 second steps. A reset time delay
setting of zero will cause the reset to be disabled. A reset time delay setting less than the
reclose time setting will cause an immediate reset following the reclose attempt.

SP-79A command example: Read the second reclose and reset timer settings.

A=
SP-79A2
15.0,20.0
>



9310200893 Rev C

BE1-79A Communication Commands

4-3