Reset timers 1, 2, 3, 4, and final, Lockout timer, Rs set and reset timers – Basler Electric BE1-79A 9310200114 User Manual
Page 12: Communication port, Power supply, Contact sensing inputs, Output contacts, Environment, Reset timers 1, 2, 3, 4, and final -2, Lockout timer -2

Reset Timers 1, 2, 3, 4, and Final
Range .................................................................. 0 to 300 seconds
Increments ........................................................... 0.1 seconds
Accuracy ..............................................................
±20 milliseconds ±1%, typical
±50 milliseconds ±1%, maximum
Lockout Timer
Range .................................................................. 0 to 300 seconds
Increments ........................................................... 0.1 seconds
Accuracy ..............................................................
±20 milliseconds ±1%, typical
±50 milliseconds ±1%, maximum
RS Set and Reset Timers
Range .................................................................. 0 to 300 seconds
Increments ........................................................... 0.1 seconds
Accuracy ..............................................................
±20 milliseconds ±1%, typical
±50 milliseconds ±1%, maximum
Communication Port
Parameters .......................................................... 9600 baud, 8N1 half duplex
Protocol ................................................................ ASCII
Power Supply
Operating Range ................................................. 120 to 240 Vac
125 to 250 Vdc
Contact Sensing Inputs
Operating Range
48 Vdc, Nominal .................................................. 38.4 to 275 Vdc
125 Vdc/120 Vac, Nominal .................................. 100 to 275 Vdc, or 96 to 264 Vac
250 Vdc/240 Vac, Nominal .................................. 200 to 275 Vdc, or 192 to 264 Vac
Energizing Level .................................................. 80% of nominal
Current Draw ....................................................... 1.5 mA maximum per input
Recognition Time
Typical ................................................................. 15 ms for dc, ac (45 to 65 Hz)
Maximum ............................................................. 25 ms for dc, ac (45-65 Hz)
Dropout Time
Typical ................................................................. 15 ms for dc, ac (45-65 Hz)
Maximum ............................................................. 25 ms for dc, ac (45-65 Hz)
Output Contacts
Resistive Ratings
120 Vac: ............................................................... Make, break, and carry 7 Aac continuously
250 Vdc: ............................................................... Make and carry 30 Adc for 0.2 s, carry 7 Adc
continuously, break 0.3 Adc
Inductive Ratings
120 Vac, 125 Vdc, 250 Vdc: ................................ Break 0.3 A (L/R = 0.04)
Environment
Operating Temperature Range: ...........................
–40 to 70°C (–40 to 158°F)
Storage Temperature Range: ..............................
–40 to 85°C (–40 to 185°F)
Humidity
Qualified to IEC 68-2-38, 1
st
Edition 1974, Basic Environmental Test Procedures, Part 2: Test Z/AD:
Composite Temperature Humidity Cyclic Test
1-2
BE1-79A General Information
9310200893 Rev C