Reset Timers 1, 2, 3, 4, and Final

Range .................................................................. 0 to 300 seconds
Increments ........................................................... 0.1 seconds
Accuracy ..............................................................

±20 milliseconds ±1%, typical

±50 milliseconds ±1%, maximum

Lockout Timer

Range .................................................................. 0 to 300 seconds
Increments ........................................................... 0.1 seconds
Accuracy ..............................................................

±20 milliseconds ±1%, typical

±50 milliseconds ±1%, maximum

RS Set and Reset Timers

Range .................................................................. 0 to 300 seconds
Increments ........................................................... 0.1 seconds
Accuracy ..............................................................

±20 milliseconds ±1%, typical

±50 milliseconds ±1%, maximum

Communication Port

Parameters .......................................................... 9600 baud, 8N1 half duplex
Protocol ................................................................ ASCII

Power Supply

Operating Range ................................................. 120 to 240 Vac

125 to 250 Vdc

Contact Sensing Inputs

Operating Range

48 Vdc, Nominal .................................................. 38.4 to 275 Vdc
125 Vdc/120 Vac, Nominal .................................. 100 to 275 Vdc, or 96 to 264 Vac
250 Vdc/240 Vac, Nominal .................................. 200 to 275 Vdc, or 192 to 264 Vac
Energizing Level .................................................. 80% of nominal
Current Draw ....................................................... 1.5 mA maximum per input

Recognition Time

Typical ................................................................. 15 ms for dc, ac (45 to 65 Hz)
Maximum ............................................................. 25 ms for dc, ac (45-65 Hz)

Dropout Time

Typical ................................................................. 15 ms for dc, ac (45-65 Hz)
Maximum ............................................................. 25 ms for dc, ac (45-65 Hz)

Output Contacts

Resistive Ratings

120 Vac: ............................................................... Make, break, and carry 7 Aac continuously
250 Vdc: ............................................................... Make and carry 30 Adc for 0.2 s, carry 7 Adc

continuously, break 0.3 Adc

Inductive Ratings

120 Vac, 125 Vdc, 250 Vdc: ................................ Break 0.3 A (L/R = 0.04)

Environment

Operating Temperature Range: ...........................

–40 to 70°C (–40 to 158°F)

Storage Temperature Range: ..............................

–40 to 85°C (–40 to 185°F)

Humidity

Qualified to IEC 68-2-38, 1

st

Edition 1974, Basic Environmental Test Procedures, Part 2: Test Z/AD:

Composite Temperature Humidity Cyclic Test

1-2

BE1-79A General Information

9310200893 Rev C