1 ampere ct, Analog to digital converter, Power supply – Basler Electric BE1-CDS240 General Information User Manual
Page 25: Option 1, Option 2, Option 3, Frequency range, Burden, Output contacts, Contact-sensing inputs

1 Ampere CT
Continuous Rating .......................................................... 4 A
One second rating .......................................................... 80 A
For other current levels, use the formula I = (K/t)
½
where t = time in seconds and K = 6,400.
Begins to Clip (saturate) ................................................. 30 A
Burden ............................................................................ <22 mΩ at 1 Aac
Analog to Digital Converter
Type ................................................................................ 16-bit
Sampling Rate ................................................................ 144 samples per cycle into digital filter
Digital Filter Output ......................................................... 24 samples per cycle
Frequency Tracking ........................................................ 40 to 63 Hz
Power Supply
Option 1
48, 110, and 125 Vdc ..................................................... Range 35 to 150 Vdc
67, 110, and 120 Vac ..................................................... Range 55 to 135 Vac
Option 2
110, 125, and 250 Vdc ................................................... Range 90 to 300 Vdc
110, 120, and 240 Vac ................................................... Range 90 to 270 Vac
Option 3
24 Vdc ............................................................................. Range 17 to 32 Vdc
Frequency Range
Options 1 and 2 only ....................................................... 40 to 70 Hz
Burden
Options 1, 2, and 3: ........................................................ 12 W continuous, 16.5 W maximum with all
outputs energized
Output Contacts
Make and Carry for Tripping Duty .................................. 30 A for 0.2 seconds per IEEE C37.90; 7 A
continuous
Break Resistive or Inductive ........................................... 0.3 A at 125 or 250 Vdc (L/R = 0.04 maximum)
Contact-Sensing Inputs
Turn-On Voltage
Contact-sensing turn-on voltages are listed in Table 1-1.
Table 1-1. Contact-Sensing Turn-On Voltages
Style
Option
Nominal Input
Voltage
Contact-Sensing Turn-On Voltage∗
Jumper (L)
(Low Position) †
Jumper (H)
(High Position)†
Jumper Not
Installed†
xxxx1xxxxxx 48 Vdc or 125 Vac/dc
26 to 38 Vdc
69 to 100 Vdc
56 to 97 Vac
n/a
xxxx2xxxxxx
125/250 Vac/dc
69 to 100 Vdc
56 to 97 Vac
138 to 200 Vdc
112 to 194 Vac
n/a
xxxx3xxxxxx
24 Vdc
n/a
n/a
Approx. 5 Vdc
∗
AC voltage ranges are calculated using the default recognition time (4 ms) and debounce time (16 ms).
† Voltage ranges depend on Jumper configurations. See Section 3, Input and Output Functions, Contact
Sensing Inputs.
9365200990 Rev M
BE1-CDS240 General Information
1-23