Operational Specifications
Metered Current Values and Accuracy
Current Range
5 Aac Nominal .......................................................... 0.5 to 15 Aac
1 Aac Nominal .......................................................... 0.1 to 3.0 Aac
Accuracy
IA, IB, IC, IG (Measured)..........................................
±
1% of reading, ±1 least significant digit at 25°C
3I0, IQ (Calculated) ..................................................
±
4% of phase reading, ±1 least significant digit at 25°C
Temperature Dependence
IA, IB, IC, IG (Measured).......................................... ≤ ±0.02% per °C
3I0, IQ (Calculated) .................................................. ≤ ±0.06% per °C
Phase Angle ................................................................... ±1° of reading, ±1 least significant digit at 25°C
Metered Voltage Values and Accuracy
Voltage Range
3 Wire Sensing ......................................................... 0 to 300 V
L-L
4 Wire Sensing ......................................................... 0 to 300 V
L-L
Accuracy (50 V to 300 V)
VA, VB, VC (Measured) .................................................. ±0.5% of reading, ±1 least significant digit at 25°C
V1, V2, 3V0 (Calculated) ................................................ ±4% of reading, ±1 least significant digit at 25°C
Temperature Dependence
VA, VB, VC (Measured) .................................................. ≤ ±0.02% per °C
V1, V2, 3V0 (Calculated) ................................................ ≤ ±0.06% per °C
Phase Angle ................................................................... ±1% of reading, ±1 least significant digit at 25°C
Metered Frequency Values and Accuracy
Frequency Range ........................................................... 10 to 75 hertz
Accuracy ......................................................................... ±0.01 hertz, ±1 least significant digit at 25°C
Sensing Input
3 Wire Sensing ......................................................... Phase A - B
4 Wire Sensing ......................................................... Phase A - Neutral
Minimum Frequency Tracking Voltage ........................... 10 V rms
Calculated Values and Accuracy
Demand
Range ............................................................................. 0.1 to 1.5 nominal
Type ................................................................................ Exponential
Accuracy ......................................................................... ±1% of reading, ±1 digit at 25°C
Temperature Dependence .............................................. ≤ ±0.02% per °C
Interval ............................................................................ 1 to 60 min
True Power
Range
5 Ampere CT ............................................................ −7,500 kW to +7,500 kW
1 Ampere CT ............................................................ −1,500 kW to +1,500 kW
Accuracy ......................................................................... ±1% at unity power factor
Reactive Power
Range
5 Ampere CT ............................................................ −7,500 kvar to +7,500 kvar
1 Ampere CT ............................................................ −1,500 kvar to +1,500 kvar
Accuracy ......................................................................... ±1% at zero power factor