beautypg.com

Differential protection application considerations, General, Be1-cds240 solution – Basler Electric BE1-CDS240 General Information User Manual

Page 10

background image

Differential Protection Application Considerations

The principle of current differential relaying is simple in concept. Measure the current flowing into the

protected zone and the current flowing out of the protected zone. These should match exactly (sum to

zero). If they do not, there is a fault within the protected zone. The mismatch in current that results from

the instantaneous summation of the currents into and out of the zone of protection is called the differential

current or the operate current. While the concept is simple, several difficulties present challenges to the

application of this type of protection. The BE1-CDS240 Current Differential System provides several

features that allow it to easily address these complications and enable it to be used in all differential

applications including transformer protection.

Problem 1: False Differential Current Due to Poor CT Performance
General

The principle of current differential relaying requires accurate measurement of the currents entering and

exiting the zone of protection. During fault conditions where high current is flowing through the zone of

protection, a CT may saturate and not faithfully reproduce the current flowing in the primary system. This

will cause a false differential current to be seen by the differential relay.

BE1-CDS240 Solution

The percentage restrained differential characteristic, shown in Figure 1-1, is applied in this application.

The differential current required to cause a trip is a percentage of the restraint current. The restraint

current is a measure of the current flowing into or through the zone of protection. Thus for higher levels of

restraint current, where the CTs may be subject to saturation, higher levels of differential current must be

seen to cause a trip. The percentage restraint is often called the slope characteristic.

Figure 1-1. Restrained Differential Characteristic


The BE1-CDS240 relay has two settable restraint current calculation methods: average and maximum.

Average restraint emulates the operating characteristics of common electromechanical relays. Maximum

restraint is recommended because it uses the current from the best performing CT to determine the

restraint to use during a fault condition. In addition, digital technology provides a transient monitor function

that enables the BE1-CDS240 relay to detect the onset of CT saturation to ride through the condition to

further enhance security from misoperation caused by poorly performing CTs.
Finally, Basler Electric addresses the source of false differential current at its roots. Active CT technology

used on the current inputs provides low burden to extend the linear range of power system CTs and wide

dynamic range to reduce measurement errors at high current levels. Sixteen bit ADC performance and

digital anti-aliasing filters also contribute to minimizing magnitude and angle measurement errors.

1-8

BE1-CDS240 General Information

9365200990 Rev M