Installation – Avalon Firestyles AGP Pellet User Manual
Page 16
16
Installation
(For Qualified Installers Only)
© Travis Industries
4141230
100-01341
Mobile Home Requirements
Outside air is required (used for combustion) - see the directions below.
DO NOT INSTALL IN SLEEPING ROOM.
CAUTION:
THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL, AND
CEILING/ROOF MUST BE MAINTAINED.
Outside Air (Used for Combustion
Use Part #99200136)
Travis Industries strongly recommends outside air for all installations, especially for those with
relatively air-tight homes.
Must not be drawn from an enclosed space (garage, unventilated crawl space).
Must not be over 48” (1220mm) long
Must be made with 1-¾” (45mm) diameter or larger metal or aluminum duct with a metal screen
attached to the end to keep out rodents (P.V.C. or other combustible materials may not be used).
We recommend the Travis Industries Outside Air Kit (part # 99200136 – additional duct may be
required).
Must have a rain cap or down-turned elbow to prevent water from entering.
Must be located so that it will not become plugged by snow or other material.
Outside air may be drawn
through the ash cleanout.
Seal this area with silicone
and/or insulation.
Outside air may be drawn from the chimney cavity.
Make sure to include an air opening at the top of the
chimney. Use a non-combustible block-off plate or
barrier (insulation) to seal the chimney from the
fireplace.
Maximum Outiside Air
Length is 48" (1220mm)