Installation (for qualified installers only), Fireplace placement requirements, Minimum framing dimensions – Avalon Firestyles 21 DV RV User Manual

Page 9: Clearances

background image

Installation (for qualified installers only)

9

© Travis Industries

4060517

100-01158

Fireplace Placement Requirements

Minimum Framing Dimensions

The fireplace requires a 1/2" space between the fireplace and the framing members (or other
materials) along the sides and back of the fireplace. The stand-offs (and nailing brackets) may
contact the framing members but no material may be placed into the 1/2" space.

Route the electrical line to a position
to the right rear of the fireplace.

Thermostat or Remote
Control Wire (either side)

27-1/4"

Vent Clearances:
1" to the sides, 1" below, and 3" above
the vent to combustibles.

20-1/4"

34-1/4"

12-3/4"

Firestop

(required)

HINT: we recommend reinforcing the
upper corners of the fireplace opening.

4-3/4"

3-5/8"

NOTE: The rear vent may require extra
clearance - make sure to accommodate the
vent when determining the framing.

Center of Rear Vent

WARNING: A cut-out for the gas line
will be required on the framing. See
the dimensions on page 6 and "Gas
Line Connection" for details.

Fireplace must be installed on a level surface capable of supporting the fireplace and vent

Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or
carpet)

This heater may be placed in a bedroom. Please be aware of the large amount of heat this
appliance produces when determining a location.

Clearances

When installed, walls in front of the fireplace must be a minimum 1" to the side of the
faceplate.

Due to the high temperature, the heater should be located out of traffic and away from furniture
and draperies.

Fireplace must be placed so the vents below and above the glass do not become blocked