Installation (for qualified installers only), Vent configurations with vertical termination – Avalon Firestyles 21 DV RV User Manual
Page 18
![background image](https://www.manualsdir.com/files/772730/content/doc018.png)
18
Installation (for qualified installers only)
© Travis Industries
4060517
100-01158
Vent Configurations with Vertical Termination
•
The diffuser must be removed.
•
The termination must fall within the shaded area shown in the chart. Use the indicated restrictor
position.
•
One 45° or 90° elbow may be used between horizontal sections (the maximum number of elbows is
three).
5 feet
10 feet
15 feet
20 feet
25 feet
30 feet
0 feet
40' (max)
5 feet
10 feet
0 feet
5 feet
10 feet
14' (max)
15 feet
20 feet
25 feet
30 feet
0 feet
0 feet
NOTE:
Horizontal sections require a
1/4" rise every 12" of travel.
10 feet
40' (max)
14' (max)
NOTE:
Restrictor positions are
based upon lab tests.
The ideal restrictor
position may vary
slightly, especially when
the termination is near a
demarkation line.
5 feet
NOTE:
One 45° or 90° elbow may
be used between horizontal
sections. Horizontal length
is caculated by adding each
horizontal run together.
35 feet
35 feet
Restrictor
Position # 1
Restrictor
Position # 6
Restrictor
Position # 7
6' (min)
6' (min)
NOTE:
Two 45° elbows
may be used.