34 installation, Top vent configuration with vertical termination, For qualified installers only) – Avalon Firestyles 564 Diamond-Fyre GSR2 Installation User Manual
Page 34
34 Installation
(for qualified installers only)
© Travis Industries
4140926
100-01395
Top Vent Configuration with Vertical Termination
The termination must fall
within the shaded area
shown in the chart. Use
the indicated restrictor
and diffuser positions.
Up to four elbows (45° or
90°) may be used.
Only one horizontal
elbow may be used.
May use 8" (203mm) or
6-5/8" (168mm) diameter
vent (see page for 25
details).
5 feet (1.5m)
0 feet
0 feet
5 feet (1.5m)
0 feet
20 feet (6m)
20 feet (6m)
5 feet (1.5m)
10 feet (3m)
5 feet (1.5m)
10 feet (3m)
0 feet
15 feet (4.5m)
20' max (6m)
10 feet (3m)
15 feet (4.5m)
15 feet (4.5m)
20' max (6m)
10 feet (3m)
15 feet (4.5m)
40' max (12m)
Exhaust Restrictor # 5
Intake Restrictor # 2
Diffuser Position # 2
25 feet (7.5m)
30 feet (9m)
35 feet (10.5m)
40' max (12m)
25 feet (7.5m)
30 feet (9m)
35 feet (10.5m)
Exhaust Restrictor # 4
Intake Restrictor # 2
Diffuser Position # 2
Exhaust Restrictor # 2
Intake Restrictor # 1 (stock)
Diffuser Position # 2
This is considered a horizontal
elbow (it does not matter
whether it turns right or left).
It may be a 90° or 45° elbow.
This is considered a
vertical elbow
Horizontal length is calculated by adding
both lengths of horizontal run
(Horizontal Length = H1 + H2).
H1
H2