8 stove installation, Floor protection requirements, Stove placement requirements – Avalon Firestyles 1250 Wood Stove User Manual
Page 8: Clearances

8 Stove
Installation
(for qualified installers only)
© Travis Industries
100-01178
4081029
Floor Protection Requirements
Stove must be placed on the Travis Industries legs or pedestal.
Floor protection must extend to the sides, rear, and front of the stove (see “Clearances” below for
minimum floor protection).
NOTE: When installed with reduced-clearance connector, the clearance to the backwall may be less
than the floor protection requirement. In this case the floor protection must extend to the wall.
Floor protection must be non-combustible and at least .018" thick (26 gauge).
Stove Placement Requirements
Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or
other means approved by local building or fire officials.
Stove must be placed so that no combustibles are within, or can swing within (e.g., drapes, doors),
36" (914mm) of the front of the stove.
If the stove is placed in a location where the ceiling height is less than 7' (2134mm), it must follow the
requirements in the section "Alcove Installation Requirements".
Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):
Clearances
The following clearances must be met (see Figure 3 and Figure 4)
Clearance Requirements:
Singlewall Connector
Reduced Clearance*
A
Sidewall to stove
18"
457mm
18"
457mm
B
Backwall to stove
18”
457mm
10-1/2" 267mm
C
Cornerwall to stove
10"
254mm
10"
254mm
D
Connector to sidewall
27"
686mm
26-1/2" 673mm
E
Connector to backwall
19-1/4" 489mm
11-1/4" 286mm
F
Connector to cornerwall
17-3/4” 451mm
17-1/4” 438mm
G
Side & Rear Floor Protector
6” 152mm (US)
8” 200mm (Canada)
6” 152mm (US)
8” 200mm (Canada)
H
Front Floor Protector
16” 406mm (US)
18” 450MM (Canada)
16” 406mm (US)
18” 450MM (Canada)
*Reduced clearance installations require one of the chimneys and connectors listed below:
AMERI-TEC model DCC with model HS chimney
DURAVENT model DVL with DURATEC or DURA-PLUS chimney
GSW Super Chimney Twenty-One connected directly to appliance
I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector
METALFAB model DW connector with TG chimney
OLIVER MACLEOD PROVENT model PV connector with model 3103 chimney
SECURITY model DP connector with SECURITY model ASHT or S2100 chimney
SELKIRK METALBESTOS model DS connector with model SSII chimney
Standard Masonry Chimney with any one of the above listed connectors
NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be
required.
NOTE: Mobile Home installations must use the reduced clearance connector and clearances listed above.
NOTE: Standard residential installations with reduced clearance connector may use the “Connector to Wall”
clearance determined by the connector manufacturer if approved by local code. This clearance is
established by the connector manufacturer and falls under the connector manufacturer’s listing. “Stove to
Wall” clearances must always be met.