Stove installation, For qualified installers only), Interior or exterior masonry chimney – Avalon Firestyles 1250 Wood Stove User Manual
Page 17
![background image](https://www.manualsdir.com/files/772701/content/doc017.png)
Stove
Installation
(for qualified installers only)
17
© Travis Industries
100-01178
4081029
Hearth Stove Direct
Connection
NOTE:
This type of installation is
not allowed in Canada.
NOTE:
Direct connections require
installation of an airtight,
non-combustible block-off
plate or damper adapter.
Figure 16
Interior or Exterior
Masonry Chimney
NOTE:
This type of installation is
not allowed in Canada.
NOTE:
This type of installation
requires a UBC approved
masonry connector or
other method approved by
the NFPA 211 standard.
See Chimney Connector
Requirements on page 10
for further details.
Figure 17
Block-off plate or
damper adapter
Remove damper
or wire it open
Airtight
Insulated
Clean-Out
Stainless steel
chimney connector
must Extend 1' past
the block-off plate or
to the flue liner
NOTE: The chimney must have a clay tile
liner. If it does not, the installation must use
a positive connection (full reline). The entire
fireplace and chimney must be clean,
undamaged, and meet all local building
codes (UBC, etc.). Damage must be
repaired prior to installation. The chimney
must be 15' (4.57M) to 33' (10.05M) tall.
Clay
Liner
Floor Protection
(See the section
"Floor Protection
Requirements" for
more details)
Combustible Mantle
Min. 18"
(457mm)
See the section
"Stove Placement
Requirements" for
minimum clearances
required.
Make sure the
clean-out seals in
place.
Clay Liner
See the section "Stove
Placement Requirements" for
minimum clearances required.
Min. 18"
(457mm)
clearance
to ceiling
This type of
installation requires
a UBC approved
masonry connector
or a factory built
(U.L. Listed) wall
thimble.
Chimney connector sections
NOTE: The chimney must have a
clay tile liner. If it does not, the
installation must use a positive
connection (full reline). The entire
fireplace and chimney must be
clean, undamaged, and meet all
local building codes (UBC, etc.).
Damage must be repaired prior to
installation. The chimney must be
15' (4.57M) to 33' (10.05M) tall.
See the section
"Floor Protection
Requirements"