10 stove installation, Chimney connector requirements – Avalon Firestyles 1250 Wood Stove User Manual
Page 10
10 Stove
Installation
(for qualified installers only)
© Travis Industries
100-01178
4081029
Chimney Connector Requirements
Chimney connector is required from the flue collar of the stove to the factory-built chimney (see
Figure 6) or masonry chimney (see Figures 13, 14, and 15).
The chimney connector must be 6” diameter and a minimum 24 gauge black steel or one of the
reduced-clearance connectors listed on page 8.
NOTE: Aluminum or galvanized steel is not allowed – these materials cannot withstand the flue
temperatures and may give off toxic fumes when heated.
NOTE: Standard residential installations may use single-wall connector (mobile homes may not).
The chimney connector may not pass through a ceiling, attic, roof, closet, or any other concealed
space (use listed UL 103 HT chimney – see “Chimney Requirements for details). DO NOT USE
CONNECTOR PIPE AS CHIMNEY.
The chimney connector should be as short and direct as possible. No more than 180
o
of elbows (two
90
o
elbows, or two 45
o
& one 90
o
elbow, etc.) may be used for the entire system (connector and
chimney). Horizontal runs should slope upwards 1/4” (6mm) per foot (305mm) and be a maximum
36” long (914mm).
The chimney connector must be installed with the crimped end pointing downwards (see Figure 5).
This prevents creosote from leaking to the exterior of the pipe.
Figure 5
The chimney connector must be fastened to the stove and each adjoining section (and chimney).
On singlewall pipe
the crimped end
points downward.