can cause air flow problems. These slide-in dampers
require that the damper frame be inside the duct. Imag-
ine an 8 x 10 rectangular duct using a slide in damper
with a frame thickness of 1”. The frame alone would
reduce the opening to 6 x 8.

Another possible problem encountered with rectangu-
lar dampers is the blade width. Many damper manufac-
turers supply dampers with 6” or 8” dampers blades.
This can become a major problem, for example, if the

Rectangular Dampers
Auto-Zone rectangular dampers are high quality alu-
minum construction with opposed/air foil designed
blades for superior control and have both blade and jamb
seals for tight shut off. The dampers are installed using
a mounting flange. The purpose for the flange mount-
ing is to allow as much unrestricted free space within
the duct as possible.

Many companies utilize slide-in type dampers which

Bypass & Slave Dampers

Zone Dampers

Table 1-1: Round Damper Selection Data

Damper Round Duct Size

(Area Ft

2

)

6”

(0.188)

8”

(0.338)

10”

(0.532)

12”

(0.769)

14”

(1.050)

16”

(1.375)

CFM @ 1” Velocity Pressure

Air Flow Probe “K” Factor- For Pressure

Independent Applications Only

474

950

1417

2120

2908

3700

Velocity Through Zone Damper

FPM

Airflow Through Zone Damper - CFM

(

∆P

S

inches W.C. With Air Damper Full Open)

750 - Zone

141

(0.03)

254

(0.02)

399

(0.01)

577

(0.02)

788

(0.01)

1031

(0.01)

1000 - Zone

188

(0.05)

338

(0.03)

532

(0.02)

769

(0.03)

1050

(0.02)

1375

(0.01)

1250 - Zone

235

(0.07)

423

(0.04)

665

(0.03)

961

(0.04)

1313

(0.03)

1718

(0.02)

1500 - Zone

282

(0.09)

507

(0.06)

798

(0.04)

1154

(0.05)

1575

0.04)

2062

(0.03)

1750 – Bypass Only

329

(0.12)

592

(0.08)

931

(0.06)

1346

(0.06)

1838

(0.05)

2405

(0.04)

2000 – Bypass Only

376

(0.15)

676

(0.10)

1064

(0.07)

1538

(0.07)

2100

(0.07)

2749

(0.05)

2250 – Bypass Only

423

(0.18)

761

(0.13)

1197

(0.09)

1730

(0.09)

2363

(0.08)

3094

(0.06)

WattMaster reserves the right to change specifications without notice

1/2" Foil Faced

Insulation

Actuator

Round Damper

Blade Assembly

Control Enclosure

(Cover Removed)

AIR

FLOW

AIRF

LO

W

Bypass & Slave Interface

1/2" Foil Faced

Insulation

Actuator

Zone Controller

Round Damper

Blade Assembly

Control Enclosure

(Cover Removed)

AIR

FLO

W AIR

FLO

W