Vent clearances – DVS -30-2 User Manual

Page 17

background image

13369-1-0203

Page 17

Figure 27

A =

*Clearance above grade, veranda, porch, deck or balcony
[*12 inches (30cm) minimum]

B =

clearance to window or door that may be opened [*12
inches (30cm) minimum for appliances < 100,000 Btuh
(30kW)

36 inches (90cm) minimum for appliances > 100,000
Btuh (30kW)]

C =

clearance to permanently closed window [minimum 12
inches (30cm) recommended to prevent condensation on
window]

D =

vertical clearance to ventilated soffit located above the
terminal within a horizontal distance of 18 inches (46 cm)
from the top of the terminal

E =

clearance to unventilated soffit [12 inches 30cm) minimum]

F =

clearance to outside corner [12 inches (30cm) minimum]

G =

clearance to inside corner [9 inches (22.5cm) minimum]

H =

*not to be installed above a meter/regulator assembly
within 3 feet (90cm) horizontally from the center-line of
the regulator

I =

clearance to service regulator vent outlet [*6 feet (1.8m)
minimum]

J =

clearance to non-mechanical air supply inlet to building or
the combustion air inlet to any other appliance [*12 inches
(30cm) minimum for appliances

100,000 Btuh (30 kW)

36 inches (90cm) minimum for appliances > 100,000 Btuh
(30kW)]

K =

clearance to a mechanical air supply inlet [* 6 feet (1.8m)
minimum]

L =

†clearance above paved sidewalk or a paved driveway
located on public property [*7 feet (2.1m) minimum]

M =

clearance under veranda, porch, deck, or balcony [*12
inches (30cm) minimum ¥]

a vent shall not terminate directly above a sidewalk or
paved driveway which is located between two single
family dwellings and serves both dwellings*

¥

only permitted if veranda, porch, deck, or balcony, is fully
open on a minimum of 2 sides beneath the floor*

*

as specified in CGA B149 Installations Codes or ANSI
Z223.1. Note: Local Codes or Regulations may require
different clearances.

VENT CLEARANCES