LOAD
Normally closed contact
2 Amp maximum
Minimum load 100mA
Normally open contact
6 Amp fluorescent lighting and resistive
3 Amp compact fluorescent lighting
3 Amp low energy lighting
3 Amp low voltage lighting (switch primary of transformer)
Fluorescent lighting (max 6 fittings recommended)
For fluorescent lighting total power factor correction ca-
pacitance must not exceed 40μF.
3 Amp fans and ventilation equipment
Switch SON lighting loads via a contactor
Minimum load 100mA
SUPPLY VOLTAGE
220-240 Volts AC 50 Hz
TIME OUT PERIOD
Adjustable 10s to 30m
LIGHT LEVEL
Light to dark
TERMINAL CAPACITY 2.5 mm
2
MATERIAL
Flame retardant ABS
TYPE
Class 2
TEMPERATURE
-10°C to 35°C
CONFORMITY
EMC-89/336/EEC
Part Numbers
Specification
Detection Pattern
EBDSPIR-VFC
Ceiling mounted
presence detector
voltage free out-
put contact
DBB
Surface mounting
back box
Ref #WD234 Issue 3