beautypg.com

Installation, Readback function, Unlcdhs handset only) – CP Electronics EBDSPIR-HB-PRM User Manual

Page 4

background image

4

Installation

The EBDSPIR-HB-PRM is designed to be mounted using either:

Flush fixing, or
Surface fixing, using the optional Surface Mounting Box (part no. DBB).

Both methods are illustrated below.

The UNLCDHS has the ability to read back the settings stored in a device.
To read back individual parameters

Navigate to the parameter and press the ‗R‘ (Read) button whilst pointing at the device. The handset will click
when the parameter has been read back, the device will flash its LED, and the value will be shown against the
parameter in the menu.

To read back all of the parameters in a menu

Press and hold the ‗R‘ (Read) button for more than 1 second.
The handset will click every time a parameter is received
The device will show multiple flashes of its LED
All of the values will be shown against the parameters in the menu.
The individual parameters may be edited and then saved as a ‗Macro‘.

Notes

If a parameter(s) has been missed because of a communication error, the missing value(s) is replaced by dashes.
When reading back, the Channel 1 relay (where fitted) will temporarily be switched off, and will return to it’s
normal state 2 seconds after the read back has been completed.

Readback function

(UNLCDHS handset only)

Flush Fixing

Surface Fixing

1

2

3

2

3

4

1

Hole Ø64mm

Warning - be careful
bending springs when
mounting unit.

4

Pull out spring tab and rotate
spring arm as shown

50mm or 60mm fixing centres

Important
Ensure that the cables are formed as shown
before affixing the cable clamp. The clamp
MUST clamp the outer sheath(s) only.

Bend cores as shown.

Wire stripping details