Programming – CP Electronics EBDSPIR-HB-PRM User Manual
Page 6

page 6
4. Programming
All the following functions can be programmed using the remote control DD-LCDHS-LR handset:
1.
Detector Parameters (factory default in brackets):
1.1
Time adjustment (20 min)
10 seconds to 99 minutes time delay (select 0 for 10 second
delay – use for commissioning only).
1.2
Sensitivity On (9)
Sensitivity level when the detector is already operational
adjustable between 1 (min.) and 9 (max.)
1.3
Sensitivity Off (9)
Sensitivity level for switching the detector on – adjustable
between 1 (min.) and 9 (max.).
1.4
Power Up On (Y)
Select No for a 30 second delay on start up. If Yes is selected,
there will be no delay on start up and the detector will always
power up detecting.
1.5
Walk Test (N)
An LED behind the detector lens will flash to show movement
has been detected (use for commissioning).
1.6
Disable Detector (N)
Disables detection. In this mode the detector acts as a
photocell only. The lux preset determines the light level at
which the output is turned on. The sensitivity preset
determines the light level at which the output turns off. The
time preset prevents nuisance tripping and in this mode is
adjustable between 0-13 minutes.
1.7
Factory Default
Restores factory default settings.
2. Switching functions (factory default in brackets):
2.1 Presence detection
Auto switch on with detection, auto off after movement ceases
(default)
and time delay ends.
2.2 Absence detection
Manual switch on, auto off after movement ceases and time
delay ends.
2.3 Switch level on (9)
Lux level setting to prevent the luminaires being switched on if
the ambient light level is sufficient (adjustable between 1
and 9). The luminaires will always be switched on at level 9.
2.4 Switch level off (9)
Lux level setting to switch the luminaires off during occupancy
if the ambient light level goes above the setting (adjustable
between 1 and 9). Level 9 will always keep the lights on. This
setting can be used for ―window row switching‖.
3
User Menu
DD-LCDHS-LR user menu:
3.1
Lux up
Can only be used with the set button—see 3.6.
3.2
Lux down
Can only be used with the set button—see 3.6.
3.3
Override on
Permanently overrides the luminaire output on.
3.4
Override off
Permanently overrides the luminaire output off.
3.5
Cancel
Cancels the on or off override, returning the detector to normal operation.
3.6
Set
Send before using lux up or lux down. The switch level on (see 2.3) can
then be adjusted using the lux up or lux down buttons.