7. Detection Patterns and Aisle Mounting
8. Fault Finding
LOAD DOES NOT COME ON 
 
Check to see if the live supply to the circuit is good. 
Strap across the L and LIVE OUT terminal to turn 
the load on. 
 
If the supply and wiring are good, check the LUX 
level setting. Increase the LUX level setting to allow 
the controller to turn on at higher ambient natural 
light level. 
 
If the detection range is smaller than expected, 
check the diagram above. Rotating the sensor 
slightly may improve the range. 
 
LIGHTS DO NOT GO OFF 
 
Ensure that the area is left unoccupied for longer 
than the selected timer setting. 
 
Make sure that the sensor is not adjacent to circulat-
ing air or heaters. 
Formula 
 
Range at Xm = (X/15 x 6) x 0.85 
Height
Range
15m
5.1m x 5.1m
12m
4.0m x 4.0m
10m
3.4m x 3.4m
8m
2.7m x 2.7m
6m
2.0m x 2.0m
Aisle Mounting