background image

4

Warning - be careful bending springs when mounting unit.

Warning - be careful bending springs when mounting unit.

4. Fixing - Flush

5. Fixing - Surface

1

4

2

5

1

4

3

2

Hole Ø74mm

Hole Ø30mm MAX

50mm or 60mm

fixing centres

Attach cable clamp.

Pull out spring tab and rotate

3

2 x VitessePlus RJ45

Connections

for Cat 5 patch leads

MWS3A-DBB required

9

4. Press and hold the left arrow key. On the main menu (―Detector Param‖ will be

showing), scroll right until the ―Ch2(dim) Set‖ menu appears on the DD-LCDHS
handset, and press ―on‖, then scroll left and right through the menu to see the
following parameters:


(Factory default settings are shown in brackets):
4.1
Light level (999)

Maintained illuminance level (adjustable between 1 and
999). At 999 the output will be always be at maximum.

4.2 Off value (99)

Always ensure that this is set to 99.

4.3 Speed on (40)

Determines the dimming response speed after the setup
time has finished. Measured in 0.1 sec intervals.

4.4 Speed set (5)

Determines the dimming response speed during the set up
time. Measured in 0.1 sec intervals.

4.5 Set seconds (120)

Determines how long the dimming response set-up period
lasts on power-up or on setting change (adjustable between
1 and 999 seconds). This enables the desired lux level to be
achieved rapidly when the lights come on, or during setup.

Dimming functions are continued on Page 10

Dimming functions

8. Programming (continued)

Using the Programming Handset (Part No. DD-LCDHS)