Basic programming – CP Electronics VITM6-EBDSPIR-DD User Manual
Page 8

8
Basic programming
Parameter 
Name 
Default 
Value 
0
1
2
3
UHS5 Handset Graphics
Description
Button Activation
On / Raise
On
Raise
Turn lights on or to raise lights.
Off / Lower
Off
Lower
Turn lights off or to lower lights.
Walk test
Off
On
Off
When set to On this causes a red LED to flash on 
the sensor when it detects movement. Use this 
feature to check for adequate sensitivity levels. 
Time Out 
(Time 
adjustment) 
20 mins
1, 10 & 
20 
minutes 
5, 15 & 
30 
minutes 
10 
seconds 
Once the detector is turned on, this value sets 
how long the lights will stay on once movement 
has ceased. 
Lux on 
level 
(Switch 
level on) 
9
2, 5 & 7
4, 6 & 9
Lux level setting to prevent the luminaires being 
switched on if the ambient light level is sufficient 
(adjustable between 1 and 9). The luminaires will 
always be switched on at level 9. 
Light Level 6 (600)
2 (200) 
5 (500) 
7 (700) 
4 (400) 
6 (600) 
9 (999) 
Sets a target light level to be maintained by the 
lighting system. 
9 (999) = disabled. 
Lux off 
level 
(Switch 
level off) 
9
2, 5 & 7
4, 6 & 9
Lux level setting to switch the luminaires off during 
occupancy if the ambient light level goes above 
the setting (adjustable between 1 and 9). Level 9 
will always keep the lights on. This setting can be 
used for “window row switching”. 
Note: the Lux Off Level value must always be 
greater than the Lux On Level value. 
Load Type
DALI
2-DALI 
7-DSI 
2-DALI 
on 
Sets the ballast control protocol to be used by the 
output channel. 
Sensitivity
9
1, 5 & 9
3, 6 & 8
Sensitivity level for detecting movement. 
1 = low sensitivity 
9 = high sensitivity 
Defaults
D
Returns the unit to the default settings.
Burn-in
0
0
50
100
Determines how long the output will be at 100% 
so that lamps ‘burn-in’. The ’burn-in’ time is not 
affected by power supply interruptions. 
Presence / 
Absence 
Presence Presence Absence
Presence mode allows the output to turn on when 
movement is detected and off when movement 
ceases. Absence mode allows the output to turn 
off when movement ceases, but must be manually 
turned on first. 
Shift
Use this button to select the settings in red and 
blue signified by the ‘Shift 1’ and ‘Shift 2’ LEDs 
Number of Shift key presses
The functionality of the EBDSPIR-DD is controlled by a number of parameters which can be 
changed or programmed by any of the following devices: 
 UHS5 Infrared Handset. See below for programmable functions. 
 UNLCDHS Infrared Handset (with LCD). See user guide for full programming details. 
For most basic programming operations the UHS5 handset can be used and the following procedures 
are based on using this device. 
Point the handset at the Sensor and send the required programming commands to the unit as shown 
below. 
Valid commands will be indicated by a red LED flash. See page 1 for details of other LED responses. 
Note: other functions on the UHS5 which are not shown below are not applicable to this product. 
 
 
 
SHIFT 1 SHIFT 2
SHIFT 1 SHIFT 2
SHIFT 1 SHIFT 2
SHIFT 1 SHIFT 2
- EBDSPIR-DD EBDSPIR-DD-IP-LT30 EBDSPIR-DD-LV MWS3A-DD-LV EBDSPIR-HB-DD EBDSM-DD VITM6-MWS6-DD MWS6-DD MWS6-DD-LV VITM6-MWS3A-DD MWS3A-DD EBDSM-AD VITM6-EBDSPIR-AD EBDSPIR-AD EBDSPIR-AD-IP-LT30 MWS6SM-DD MWS6SM-AD EBDSPIR-HB-AD MWS3A-AD EBDSPIR-PRM-L3 VITMR-EBDSPIR-PRM VITMR-MWS6-PRM MWS3A-PRM-L3 VITMR-MWS3A-PRM MWS3A-PRM-VFC-LV MWS3A-PRM EBDSPIR-AD-LV MWS6-AD MWS6-PRM-L3 MWS6-PRM-VFC EBDSPIR-PRM-VFC VITM4-MWS6-PRM MWS6-PRM EBDSPIR-PRM EBDSPIR-PRM-IP EBDSPIR-PRM-IP-LT30