CP Electronics VITM4 User Manual
Page 4
4
Live supply
Earth
Neutral
Permanent
Live
Due to our policy of continual product improvement CP Electronics reserves the right to alter the specification of this product without prior notice.
Conduit box to VITM4-S mains wiring
VITM-ROSE mains wiring
VITM-ROSE connector wiring
Modules
VITM4-S
4 pole starter box
VITM4-E
4 pole extender box
VITM4-SL1
4 pole starter box with 1m lead
and ceiling rose connector
VITM4-SD5
Pre-wired corridor module with 5
metres of cable
Presence / Absence Detectors
VITM4-EBDSPIR-B
PIR presence detector
VITM4-EBDSPIR-PRM PIR presence/absence detector
VITM4-MWS3A-PRM Microwave presence/absence
detector (adjustable head)
VITM4-MWS6-PRM
Microwave presence/absence
detector (fixed head)
VITM4-EBMPIR-B
Miniature PIR presence detector
VITM4-EBMPIR-PRM Miniature PIR premium presence
detector
Accessories
VITM4-SELVMOD
SELV switching module
VITM-ROSE
Ceiling rose module
Connectors
Dual Detector Leads (LSF)
VITM4-LD3-B
3m basic sensor lead
VITM4-LD3-PRM
3m premium sensor lead
VITM4-LPW
4 pole luminaire plug white
VITM4-LPR
4 pole luminaire plug red
Luminaire Leads (LSF)
VITM4L303100W
3 core 3m 1.0mm
2
White plug
VITM4L305100W
3 core 5m 1.0mm
2
White plug
VITM4L403100R
4 core 3m 1.0mm
2
Red plug
VITM4L405100R
4 core 5m 1.0mm
2
Red plug
Other leads available to order.
Voltage
230VAC +/- 10%
Frequency
50Hz
Terminal capacity 4mm
2
in wiring compartment
Temperature
0ºC to 35ºC
Power
Rating of system 16A. Rating of each output 10A
Compliance
BS 5733:1995
For lighting purposes only with suitable circuit protection. For fixed wiring only
C.P. Electronics Ltd
Brent Crescent
London
NW10 7XR
United Kingdom
Tel:
+ 44 (0) 333 900 0671
Fax:
+ 44 (0) 333 900 0674
www.cpelectronics.co.uk
[email protected]
Ceiling rose / conduit box connection
Part numbers
Ratings
IMPORTANT NOTICE!
This device should be installed by a
qualified electrician in accordance with
the latest edition of the IEE wiring
regulations.
Ref: #WD289 Issue 5
Each pole has two screw terminals.
Each terminal accepts 1 x 2.5mm
2
Screw fixings to conduit box
Use a VITM-ROSE when there is a need to take power from a conduit box. Plug
the connector into the VITM-ROSE and wire the other end of the lead into the
terminals of the VITM4-S. A pre-wired version is available, VITM4-SL1.
UK Patent no. GB2463063
EU patent pending
EU registered design no.
001587544-0001, 001587544-0002
Live supply
Neutral
Permanent Live
Earth