3) Harmonic current capable of absorbing.
Each step is formed by 2 reactors and a 6 terminal capacitor which contains 2 three-
phase, 3 terminal capacitors each electrically insulated. The operating principle of this
design is that each reactor is connected to each of the three capacitor terminals forming
an LC set tuned to a frequency close to the 5th harmonic and another set tuned near to
the 7th harmonic. The following diagram shows how the step is formed:

Fig. 1 – Standard type at 400V 50Hz, triangle connection

L1

L2

C1

6 bornes

U11

V11

W11

U12

V12

W12

U1

V1

W1

U1

V1

W1

U2

V2

W2

U2

V2

W2

AF1

Paso pequeño: 4 bobinas por fase de 5º armónico 2 bobinas por fase de 7º armónico
Paso grande : 8 bobinas por fase de 5º armónico 4 bobinas por fase de 7º armónico

Fig. 2 – Standard type at 480V 60Hz, star connection


Filter regulation
Filter regulation is via a conventional power factor regulator as with any other standard