CIRCUTOR FAR-Q Series User Manual
Page 4

------ Absorption filter ------ User Manual,
M98206701-03-07A ------ Page 3 of 11------
R7C112 FAR5-Q8-525-400
400
8
7 x 75
820
280
140
FR8
R7C113 FAR5-Q12-562.5-400
400
8
37.5 + (7 x 75)
878
300
150
FR12
R7C114 FAR5-Q12-600-400
400
8
8 x 75
937
320
160
FR12
R7C115 FAR5-Q12-637.5-400
400
9
37.5 + (8 x 75)
996
340
170
FR12
R7C116 FAR5-Q12-675-400
400
9
9 x 75
1054
360
180
FR12
R7C117 FAR5-Q12-712.5-400
400
10
37.5 + (9 x 75)
1113
380
190
FR12
R7C118 FAR5-Q12-750-400
400
10
10 x 75
1171
400
200
FR12
Table 2.- Standard filters for 60 Hz systems
Q
CODE
TYPE (*)
VOLTAGE STEPS
STEPS x (kvar)
Irms
5
th
7th CABINET
(V)
(A) (A) (A)
R7C401 FAR5-Q6-105-400 480 3
3 x 35
166
60
30
FR6
R7C402 FAR5-Q6-140-400 480 4
4 x 35
221
80
40
FR6
R7C403 FAR5-Q6-175-400 480 5
5 x 35
276
100
50
FR6
R7C404 FAR5-Q6-210-400 480 6
6 x 35
331
120
60
FR6
R7C405 FAR5-Q6-245-400 480 4
35 + (3 x 35)
387
140
70
FR6
R7C406 FAR5-Q6-280-400 480 4
4 x 70
442
160
80
FR6
R7C407 FAR5-Q6-315-400 480 5
35 + (4 x 70)
497
180
90
FR6
R7C408 FAR5-Q6-350-400 480 5
5 x 70
552
200
100
FR6
R7C409 FAR5-Q8-385-400 480 6
35 + (5 x 70)
608
220
110
FR8
R7C410 FAR5-Q8-420-400 480 6
6 x 70
663
240
120
FR8
R7C411 FAR5-Q8-455-400 480 7
35 + (6 x 70)
718
260
130
FR8
R7C412 FAR5-Q8-490-400 480 8
7 x 70
773
280
140
FR8
R7C413 FAR5-Q12-525-400 480 8
35 + (7 x 70)
829
300
150
FR12
R7C414 FAR5-Q12560-400 480 8
8 x 70
884
320
160
FR12
R7C415 FAR5-Q12-595-400 480 9
35 + (8 x 70)
939
340
170
FR12
R7C416 FAR5-Q12-630-400 480 9
9 x 70
994
360
180
FR12
R7C417 FAR5-Q12-665-400 480 10
35 + (9 x 70)
1050
380
190
FR12
R7C418 FAR5-Q12-700-400 480 10
10 x 70
1105
400
200
FR12
1.3.- Safety warnings
This manual contains information and warnings about the FAR-Q hybrid
bank which must be followed to guarantee the proper operation of all
instrument functions and to maintain it in a safe condition.
If the instrument is not installed in accordance with manufacturer's
specifications, the instrument's protection may be damaged.
Check that the protection devices are operating correctly.
2.- MAIN FEATURES
A FAR-Q hybrid filter is formed by various groups of inductances plus a capacitor in
series, located in an appropriate cabinet. Each step is characterised by three
parameters:
1) Power factor to be corrected at 50 or 60 Hz.
2) Harmonic to be filtered, generally 5
th
and 7
th
.