Key points for inspecting the regulator, Key points for inspecting capacitors, Key points for inspecting static switches – CIRCUTOR OPTIM-EMS-C Series User Manual
Page 21: Tightening torque of the electrical connections

5.2.2. TIGHTENING TORQUE OF THE ELECTRICAL CONNECTIONS
The connections must be tight.
The tightening torques for the fuse bases are indicated in
Table 2:Torques for the power cables of the three-pole circuit breakers.
Circuit breaker
Torque (Nm)
In ≤ 3 x 63 A
2
5.2.3. KEY POINTS FOR INSPECTING STATIC SWITCHES
Check that the plastic parts are not blackened and do not show signs of burning or hardening.
Check that the head is properly inserted.
Check the tightness of cables and terminals, as shown in
Table 3:Torques of cables to semiconductors
Thyristor type
Power cable connection torque (Nm)
IXYS
3.25
The terminals must be clean.
Cleaning: In dirty environments (dust, sawdust, metal trimmings, etc.). Vacuum the dust and
solid waste regularly.
There is no estimated time frame for cleaning, it depends on the amount of dirt that penetrates
the cabinet of the capacitor bank.
5.2.4. KEY POINTS FOR INSPECTING CAPACITORS
Inspect the cables and terminals. They should not be overheated or blackened.
The terminals must be clean.
Check the tightness of the capacitor terminals, as shown in
Table 4:Torques of the cables to the capacitor terminals.
Capacitor
Torque (Nm)
CLZ FP
2
5.2.5. KEY POINTS FOR INSPECTING THE REGULATOR
Check that the regulator does not show signs of deterioration and the display is lit as normal.
Inspect the cables and terminals. They should be clean and should not be hardened or over-
heated.
Check the connections.
Check that the terminals are tightened properly. The recommended torque is
0.6 Nm.
21
Instruction Manual
OPTIM EMS-C series