CIRCUTOR DIR2 User Manual
Dir2

DIR2
Manual de Instrucciones
Instruction Manual
M98231501-20-10C
REGULADOR DE ENERGÍA REACTIVA DIR2
El DIR2 es un regulador de un solo paso de muy reducidas
dimensiones, ideal para compensar el cos
ϕ
en instalaciones
que requieren una regulación en un solo escalón. Puede
emplearse también como complemento de un regulador de
más pasos, ya sea como relé de alarma o para conectar un
paso adicional.
DIR2 PF Regulator
The DIR2 is a PF regulator to control a single capacitor step. The
DIR2 is the ideal regulator for cos
ϕ
compensation in small
installations where a single step regulation is required. The
regulator can be also used as alarm relay in case of lack of
compensation or as additional step in an existing capacitor bank.
CONEXIÓN Y AJUSTES
Para la conexión y puesta en marcha del relé DIR2, deben
tenerse en cuenta los siguientes puntos :
- El relé DIR2 requiere la instalación de un transformador de
corriente eficiente de la serie MC1 (In / 0,25 A), donde In
debe ser mayor que la intensidad total de los receptores
instalados en la línea a compensar.
- El transformador de corriente se instalará en un punto de la
acometida por el que circule la totalidad de la intensidad de la
línea a compensar, pero sin leer la intensidad propia del
condensador (ver fig.1).
- Conectar el secundario del transformador de corriente (entre
borne 1S1 y borne 1S2, 2S1 ó 2S2, según el valor de primario
de corriente adecuado a la máxima corriente de la instalación)
en los bornes señalizados como S1 y S2 en el DIR2.
- La tensión de alimentación del regulador DIR2 debe tomarse
entre fases (habitualmente entre las fases L2 y L3) y debe
conectarse a los bornes A1-A2.
- IMPORTANTE: La fase donde está instalado el
transformador de intensidad, (normalmente L1), no debe
coincidir con las fases de las que se toma la tensión de
alimentación (normalmente L2-L3).
- La intensidad reactiva de disparo del relé se fija en el mando
frontal. El relé conecta cuando la intensidad reactiva medida
supera el valor marcado. Para evitar fluctuaciones en la
operación, el relé desconecta cuando la intensidad reactiva
medida baja por debajo del 70% de dicho valor.
- Si el relé no conecta y hay carga suficiente en la instalación,
revisar las conexiones, y si son correctas, probar a
intercambiar entre sí las conexiones que van a los terminales
S1 y S2 del DIR2.
CONNECTION AND SETUP
To connect the DIR2 PF regulator, the following steps must be
considered:
- The DIR2 regulator requires one efficient current transformer
of MC1 type (In / 0.25 A). The primary current In must be
greater than the maximum current expected at the load to be
compensated.
- The current transformer must be placed in the line supplying
the load to be compensated. It must measure the load current,
excluding the capacitor current (see fig. 1)
- Connect the CT secondary terminals (between terminal 1S1
and terminal 1S2, 2S1 or 2S2, with the primary side value fitted
to the maximum value of the current drawn by the loads) to the
DIR2 terminals designated as S1-S2.
- The supply voltage of the DIR2 regulator must be taken phase
to phase (usually from phases L2 and L3) and connected to
terminals A1-A2).
- IMPORTANT: The phase where CT is placed (usually L1)
must not coincide with any of the phases used for the regulator
supply (usually L2 and L3)
- The reactive current at which the regulator trips is set by means
of the frontal knob. The output relay is activated when the
measured reactive current exceeds the set value. To avoid relay
flickering, the relay is deactivated when the current goes below
the 70% of the set value.
- If the DIR2 relay does not connect when it is expected,
(considerable reactive current at the load), review the
connections and check if it connects when reversing the
connections of CT secondary side to S1-S2 terminals.
CARACTERISTICAS TÉCNICAS / TECHNICAL CHARACTERISTICS
Tensión de alimentación : Fase - Fase
400 V ±10%
Supply voltage : Phase to Phase
Frecuencia
50-60 Hz
Frequency
Consumo
< 3 VA
Power consumption
Circuito de intensidad
Current circuit
Corriente nominal
0,25 A c.a. / a.c.
Rated current
Sobrecarga permanente
1,2 In
Maximum permanent overload
Consumo
< 0,05 VA
Power consumption
Corriente reactiva de disparo
Reactive tripping current
Margen de ajuste del disparo: C/K
0,15 ... 2
Ver ejemplo / See example
Tripping adjustment range: C/K
Retardo de conexión Tc
5 s
Connection delay Tc
Retardo de desconexión Tr
2 s
Disconnection delay Tr
Relé de salida
Output relay
Corriente térmica Ith
10 A
Thermal current Ith
AC11 Ie / Ue
10 A / 250 V c.a. / a.c.
AC11 Ie / Ue
DC11 Ie / Ue
0,3 A / 110 V c.c. / d.c
DC11 Ie / Ue
Vida mecánica
10
⋅
10
6
maniobras / operations
Mechanical endurance
Vida eléctrica
10
⋅
10
4
maniobras / operations
Electrical endurance
Condiciones ambientales
Environment conditions
Temperatura de trabajo
-10º a +50 ºC
Working temperature
Humedad relativa máxima sin condensación
95 %
Maximum relative humidity without condensation
Altitud máxima de funcionamiento
2000 m (s.n.m.) / 2000 m (AMSL) Maximum operation altitude
Otras características:
Other characteristics
Indicación de conexión:
Verde: Alimentación, Rojo: Relé conectado
LED: Verde / Rojo
Green / Red LED
Connection indication:
Green : Supply, Red: Relay ON
Fijación sobre perfil
DIN 46277 (EN 50022)
Rail fastening
Categoría de protección de la caja
IP 40
Enclosure protection category
Peso
0,25 kg
Weight
Protección al choque eléctrico
doble aislamiento clase II /
class II double isolation
Electric shock protection