DIELECTRIC STRENGTH TESTER FOR ISOLATING OILS OT2-60D --------- Page 5
 
 
2.3.
Connection cable:
It’s a standard connection cable.
 
 
 
 
 
 
 
 
 
3. INTRODUCTION 
 
The OT2-60D range is automatic equipment especially designed to test the disruptive 
voltage of isolating oils in new or used transformers, cables with oil, automatic 
switches, capacitors, etc. 
The disruptive voltage is not a basic property of the oil, but it indicates us the degree 
of contamination of this oil (water, solid materials in suspension), allowing us to decide 
on the possibility of carrying out a treatment of drying and filtration, or replacing the oil. 
The method that the OT2-60D uses can be applied to oils of nominal viscosity of up to 
350 mm
2
/s at 40ºC, according to IEC-156 standard.
The OT2-60D is supplied with a complete series of protectors making it highly 
protected and reliable. 
It is easy to handle, all buttons or illuminated switches are on the front control panel.
The test cell is especially designed to easily change the electrodes in accordance with 
the different standards in operation, the easy insertion into the registering transformer 
terminals and for its complete cleaning. 