Technical features – CIRCUTOR REC3 Series User Manual
Page 22

7�- TECHNICAL FEATURES
Power supply
Rated voltage
230V
~
Tolerance
-15%, +15%
Frequency
50Hz - 60Hz , ±5%
Maximum power consumption
5VA
Installation category
CAT III 300V
RCCB
Models
REC 3- REC 3C 2 poles
REC 3 - REC 3C 4 poles
Rated voltage
230V
~
Rated current
40 / 63 A
Sensitivity, IΔn
30 mA or 300 mA
Resistance to surges
class A , AC: 250A 8/20μs
class S: 3000A 8/20μs
Resistance to short-circuits
Inc : 10000A to 230/400V with gB 80A fuse
Class
A (IEC 61008.1)
Number of poles
2
4
Measurement circuit
The leakage current will be supervised by measuring the resistance downstream of the RCCB.
Sensitivity
Rd and Rd0
RCCB response
30 mA
Rd < 15 KΩ
no reclose
Rd0 > 23 KΩ
reclose
300 mA
Rd < 2.5 KΩ
no reclose
Rd0 > 5.0 KΩ
reclose
Outputs (REC 3C models)
Type
2 switched contacts
Rated voltage
230
~
Maximum current
0.13A
Nominal power
30 VA
User interface
LEDs
2 LEDs:
AUTO in green and REC in red
Environmental features
Operating temperature
-25ºC... +55ºC
Storage temperature
- 35ºC... +65ºC
Relative humidity (non-condensing)
5 ... 95%
Maximum altitude
2000 m
Resistance to pollution
Category 2
Protection degree
IP 20
Mechanical features
Models
REC 3- REC 3C 2 poles
REC 3 - REC 3C 4 poles
Weight
416 g
598 g
Material
V0 Polycarbonate plastic
Box colour
RAL 7035
Fixing
DIN rail
22
Instruction Manual
REC 3 - REC 3C