Technical features – CIRCUTOR CEM-M-ETH User Manual
Page 19

5�- TECHNICAL FEATURES
Power supply
Rated voltage
230 V~ ± 20%
Maximum power consumption
4 VA
Frequency
50/60 Hz with no differentiation
Insulation
AC voltage
4kV RMS 50Hz during 1 minute
Overimpulse
1�2/50ms 0Ω source impedance
6 kV at 60º and 240º, with positive and negative polarization
Memory
Setup, events, load curve
Non-volatile EEPROM memory
User interface
LED
3 LEDs (
POWER - LINK - LINL/ACT)
Communication
Communications protocol
Modbus/TCP
Environmental features
Operating temperature
-25ºC... +70ºC
Storage temperature
-35ºC... +80ºC
Relative humidity (non-condensing)
5 ... 95%
Maximum altitude
2,000 m
Mechanical features
Dimensions (mm)
Enclosure
ABS + V0 polycarbonate
Weight
115 gr
Protection degree
IP 51 installed
IP 40 in the terminal area
Standards
Safety requirements for electrical units for measurement, control and
laboratory use� Part 1: General requirements�
EN 61010-1: 2010
Electromagnetic compatibility (CEM)� Part 6-2: Generic standards�
Immunity for industrial environments�
EN 61000-6-2: 2005
Electromagnetic compatibility (CEM)� Part 6-3: Generic standards�
Emission standard for residential, commercial and light industry envi-
ronments�
EN 61000-6-3: 2007
19
Instruction Manual
CEM M-ETH