Variables modbus – CIRCUTOR CEM-M-ETH User Manual
Page 13

Table 5
shows the format of the
MODBUS/TCP frame.
Table 5: MODBUS/TCP frame format
Name
Length
Function
Transaction identifier
2
For message synchronisation between the server and client.
Protocol identifier
2
Value 0 for
MODBUS/TCP
Field length
2
Number of bytes remaining in the frame
Unit identifier
1
Peripheral number
Function code
1
Modbus function number
Data bytes
n
Response or command data
The
MODBUS functions implemented in the unit are:
Functions 03 and 04. Reading of logs.
Function 10. Writing of multiple logs.
4�4�2�- VARIABLES MODBUS
All
MODBUS map addresses are hexadecimal.
4�4�2�1�- Configuration variables
The
Read and Write functions are implemented for these variables.
Table 6:Modbus configuration variables CEM M-RS485.
Description
Address
Size
Valid data range
Default
value
Impulse output type
0x0080
16 bits
0: Active energy, 1: Reactive energy
0
Impulse output weight
0x0081
16 bits
Wh/impulse 0 ... 99999
-
Cost per kWh
0x00B0
32 bits
0.0000 ... 9999.9999 with 4 decimal places
of resolution
-
KgCO
2
0x00B2
32 bits
0.0000 ... 9.0000 with 4 decimal places of
resolution
-
Note: Some MODBUS variables may not be available depending on the CEM energy meter
coupled to the
CEM M-ETH. See “4.4.2.7.- Available addresses by unit”
13
Instruction Manual
CEM M-ETH