Variables modbus – CIRCUTOR CEM-M-ETH User Manual

Page 13

background image

Table 5

shows the format of the

MODBUS/TCP frame.

Table 5: MODBUS/TCP frame format

Name

Length

Function

Transaction identifier

2

For message synchronisation between the server and client.

Protocol identifier

2

Value 0 for

MODBUS/TCP

Field length

2

Number of bytes remaining in the frame

Unit identifier

1

Peripheral number

Function code

1

Modbus function number

Data bytes

n

Response or command data

The

MODBUS functions implemented in the unit are:

Functions 03 and 04. Reading of logs.

Function 10. Writing of multiple logs.

4�4�2�- VARIABLES MODBUS

All

MODBUS map addresses are hexadecimal.

4�4�2�1�- Configuration variables

The

Read and Write functions are implemented for these variables.

Table 6:Modbus configuration variables CEM M-RS485.

Description

Address

Size

Valid data range

Default

value

Impulse output type

0x0080

16 bits

0: Active energy, 1: Reactive energy

0

Impulse output weight

0x0081

16 bits

Wh/impulse 0 ... 99999

-

Cost per kWh

0x00B0

32 bits

0.0000 ... 9999.9999 with 4 decimal places

of resolution

-

KgCO

2

0x00B2

32 bits

0.0000 ... 9.0000 with 4 decimal places of

resolution

-

Note: Some MODBUS variables may not be available depending on the CEM energy meter

coupled to the

CEM M-ETH. See4.4.2.7.- Available addresses by unit”