6.2 Acquisitions Field
Interval:
It determines the interval between readings in the hh:mm:ss format.
New data is stored in the logger memory after each time interval.
External Battery Switch time: Defines an interval of time preceding each measurement for turning on
the power supply of external devices (4-20 mA transmitters, for
example). This feature is intended for saving power when the external
power supply is battery powered and the logging interval is long. This
signal is disabled when a measurement is completed. This time is
limited to 10 seconds and must be less than half of the interval
between readings.
Estimated time:
It informs the estimated time for the accomplishment of programmed
readings based on the logging “Interval” and on the number of
programmed readings.
Daily Repetition:
Allows loggings to be repeated everyday, for example, recording data
from 8 AM to 5 PM day after day. The start and stop times are defined
in the fields “Start time” and “Stop time.”
6.3 Start Loggings Field
Immediately:
The logger starts logging as soon as the configuration is applied. Not
valid when the option ‘Daily Repetition’ is selected.
Start via Palm:
Logging is started via Palm. The LogPalm software must be installed in
the PDA. (See Palm User under this section)
Day / Hour:
Logging starts at a defined date and time. The date defined is used for
the Daily Repetitions option as well. Through Start Button Starts and
stops logging by pressing the Star button for two seconds.
6.4 Stop Loggings Field
At Full Memory:
Loggings can be stored up to the full memory capacity is reached.
Wrap around:
Logging never stops. The LogBox-DA will keep on recording the
readings and when the memory is full it will overwrite the oldest record
in a circular or wrap around manner.
After a defined number of readings: The logger will stop logging after the number of readings here
defined is reached. Not valid when the option ‘Daily Repetition’ is
selected.
Day / Hour:
The LogBox-DA will stop logging at the user-defined date and time. Not
valid when the option ‘Daily Repetition’ is selected.