beautypg.com

Calibration for type sw style load sensors – Nexen TA100 964400 User Manual

Page 11

background image

7

FORM NO. L-20292-C-0700

NOTE

If using one Type SW Tension Sensor, Terminals 5
and 6 must be jumpered together.

1.

Set the Power Switch to ON.

2.

Make sure the web has been removed and no other
objects are sitting or resting on the sensor roll.

3.

Rotate both S1 and S2 counterclockwise to minimum
(See Figure 15).

4.

Connect a voltmeter to TP7 (COM) and TP1 (See Figure 15).

5.

Rotate Z1 to read 0.00VDC at TP1 (See Figure 15).

NOTE

If two Type SW Tension Sensors are used, proceed
with Steps 6 and 7.

6.

Connect a voltmeter to TP7 (COM) and TP2 (See
Figure 15).

7.

Rotate Z2 to read 0.00VDC at TP2 (See Figure 15).

CALIBRATION FOR TYPE SW STYLE LOAD SENSORS

NOTE

Prior to calibration, make sure jumpers J3 and J4 are set to the No. 4 position for TYPE SW Sensors.

ZERO ADJUSTMENT (WITH ONE OR TWO TYPE SW TENSION SENSORS)

FIGURE 15

Jumpers

J3 and J4

TP7

TP2

TP1

Z2

Z1

S1

S2

SPAN ADJUSTMENT (WITH ONE OR TWO TYPE SW TENSION SENSORS)

FIGURE 16

NOTE

Before making any Span adjustments, the output
voltage level needs to represent the tension levels
required. The maximum tension level needs to be
calculated (Example: Maximum Tension = 100 Lbs.).

NOTE

When using one Type SW Tension Sensor, Terminals
5 and 6 must be jumpered together.

1.

Thread a rope or narrow web over the Sensor Roll in
the normal path. Be sure the rope or web is at the
center of the Sensor roll; then, hang a known weight
(within the range of the system) on one end of the
rope or web (Example: Maximum Tension = 100 Lbs.,
hang a 50 Lb. weight) (See Figure 16).

This manual is related to the following products: