NKW 50Hz REVERSIBLE CHILLER INSTALLATION MANUAL
Compressor Resistance
Thermistor Resistance
Operating Limits
Operating Limits
Cooling
Heating
(°F)
(°C)
(°F)
(°C)
Source Side Water Limits
Min. Entering Water
30
-1.1
30
-1.1
Normal Entering Water
85
29.4
60
15.6
Max. Entering Water
110
43.3
90
32.2
Load Side Water Limits
Min. Entering Water
50
10.0
60
15.6
Normal Entering Water
60
15.6
100
37.8
Max. Entering Water
90
32.2
120
48.9
Notes:
Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units
are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependant upon three
primary factors: 1) entering source temperature, 2) entering load temperature, and 3) flow rate (gpm). When any of the factors are at
the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation. Consult the
Capacity Tables for each model to determine allowable normal operating conditions. Units are not designed for outdoor installation.
Compressor Resistance Chart
Model
380-400V
120
2.116 / 2.088 / 2.072
180
1.29 / 1.28 / 1.33
240
1.13 / 1.11 / 1.10
360
.83 / .83 / .83
600
0.52 / .52 / .52
10/7/2014
Resistance values listed in ohms and measured at 25C between phases 1-2, 1-3, 2-3, respectively.
Specialized measurement device should be used for accurate resistance readings due to low resistance values.
Thermistor Resistance
Thermistor
FX10
Temperature (°C)
Resistance (Ohms)
-15
746-770
-10
775-803
-5
808-836
0
841-869
5
875-903
10
910-938
15
946-974
20
981-1013
25
1019-1051
30
1058-1090
35
1097-1129
40
1137-1169
45
1179-1211
50
1221-1253
55
1261-1297
60
1305-1341
65
1350-1386