beautypg.com

Compressor resistance, Thermistor resistance, Compressor resistance chart – WaterFurnace Series NXW User Manual

Page 31

background image

31

ENVISION

2

NKW 50Hz REVERSIBLE CHILLER INSTALLATION MANUAL

Compressor Resistance

Thermistor Resistance

Operating Limits

Operating Limits

Cooling

Heating

(°F)

(°C)

(°F)

(°C)

Source Side Water Limits

Min. Entering Water

30

-1.1

30

-1.1

Normal Entering Water

85

29.4

60

15.6

Max. Entering Water

110

43.3

90

32.2

Load Side Water Limits

Min. Entering Water

50

10.0

60

15.6

Normal Entering Water

60

15.6

100

37.8

Max. Entering Water

90

32.2

120

48.9

Notes:

Minimum/maximum limits are only for start-up conditions, and are meant for bringing the space up to occupancy temperature. Units

are not designed to operate at the minimum/maximum conditions on a regular basis. The operating limits are dependant upon three
primary factors: 1) entering source temperature, 2) entering load temperature, and 3) flow rate (gpm). When any of the factors are at
the minimum or maximum levels, the other two factors must be at the normal level for proper and reliable unit operation. Consult the
Capacity Tables for each model to determine allowable normal operating conditions. Units are not designed for outdoor installation.

Compressor Resistance Chart

Model

380-400V

120

2.116 / 2.088 / 2.072

180

1.29 / 1.28 / 1.33

240

1.13 / 1.11 / 1.10

360

.83 / .83 / .83

600

0.52 / .52 / .52

10/7/2014

Resistance values listed in ohms and measured at 25C between phases 1-2, 1-3, 2-3, respectively.

Specialized measurement device should be used for accurate resistance readings due to low resistance values.

Thermistor Resistance

Thermistor

FX10

Temperature (°C)

Resistance (Ohms)

-15

746-770

-10

775-803

-5

808-836

0

841-869

5

875-903

10

910-938

15

946-974

20

981-1013

25

1019-1051

30

1058-1090

35

1097-1129

40

1137-1169

45

1179-1211

50

1221-1253

55

1261-1297

60

1305-1341

65

1350-1386