NKW 50Hz REVERSIBLE CHILLER INSTALLATION MANUAL

Electrical Data

Compressor Protection Module

An electronic protection module is provided with

compressors utilized in model size 150. This module will
protect against phase reversal and phase loss at start-up.
Protection is active for 5 seconds after the first second
of compressor operation. In the event that either phase
sequencing or phase loss has occurred the following
blink sequence will display on the module.

Envision Chiller (30-150kW) Electrical Table

Model

Rated

Voltage

Voltage

Min/Max

Compressor

1

Total

Unit
FLA

Min

Circ

Amp

Min

Fuse/
HACR

Max

Fuse/

HACR

2

MCC

RLA

LRA

030

380-420/50/3

340/440

19.0

12.2

87.0

24.4

27.5

30.0

35

045

380-420/50/3

340/440

19.0

12.2

110.0

24.4

27.5

30.0

35

060

380-420/50/3

340/440

27.0

19.2

140.0

38.4

43.2

45.0

60

090

380-420/50/3

340/440

38.6

24.7

197.0

49.4

55.6

60.0

80

150

380-420/50/3

340/440

62.0

39.7

260.0

79.4

89.3

100.0

125

HACR circuit breaker in USA only 10/7/14

1

- MCC, RLA, & LRA rating per compressor. Breaker & FLA sized for both compressors.

2

- Equipment supplied with Class J fuses per minimum fuse size.