1.

Leaving Air Temperature (LAT) Sensor – This 10 kOhm

NTC sensor is factory installed on all UPC equipped

heat pumps. It typically is attached to wiring inside

the blower cabinet on the suction side of the blower.

This sensor is attached on ABC FP2 pins available as

LAT AU-30.

1.

Compressor Proving Sensors – This optional factory

installed current sensor is connected to confirm

compressor operation via the power wires. The sensor

is attached at ABC Y1 and available at point BV-65.

1.

Valve End Switch – This optional input is setup for a field

installed flow valve end switch. This end switch input is

attached at ABC Y2 and available at point BV-67.

1.

Fan Proving Sensors – This optional factory installed

current sensor is connected to confirm fan operation

via the power wires. The sensor is attached at ABC G

and available at point BV-33.

1.

Occupancy Sensor - This standard feature includes a

field installed and wired room sensor with occupancy

sensor typically found in DDC systems. The RNet

room sensors can be found thru your commercial

representative. The occupancy Sensors are attached at

ABC 0 and can be found at point BV-49.

1.

Dirty Filter Switch – This optional field installed switch

is connected to confirm dirty filter operation. The

dirty filter switch can be found thru your commercial

representative. The sensor is attached at ABC W and

available at point BV-63.

2. Fault, Configuration, and Status Codes – The codes

can be visible to the BAS if desired

Fault LED (LED1, Red)

Red Fault LED

LED Flash

Code *

Lockout

Reset/

Remove

Fault Condition Summary

ABC Basic F

aults

Normal - No Faults

Off

-

Fault-Input

1

No

Auto

Tstat input error. Autoreset upon condition removal.

Fault-High Pressure

2

Yes

Hard or Soft

HP switch has tripped (>600 psi)

Fault-Low Pressure

3

Yes

Hard or Soft

Low Pressure Switch has tripped (<40 psi for 30 continuous sec.)

Fault-Freeze Detection FP2

4

Yes

Hard or Soft

Freeze protection sensor has tripped (<15 or 30 degF for 30 continuous sec.)

Fault-Freeze Detection FP1

5

Yes

Hard or Soft

Freeze protection sensor has tripped (<15 or 30 degF for 30 continuous sec.)

Fault-Condensate Overflow

7

Yes

Hard or Soft

Condensate switch has shown continuity for 30 continuous sec.

Fault-Over/Under Voltage

8

No

Auto

Instantaneous voltage is out of range. **Controls shut down until resolved.

Fault-FP1 & 2 Snsr Error

11

Yes

Hard or Soft

If FP1 or 2 Sensor Error

ABC & A

XB A

d

v

anc

ed F

aults

Fault-Compressor Monitor

10

Yes

Hard or Soft

Open Crkt, Run, Start or welded cont

Non-CriticAXBSnsrErr

13

No

Auto

Any Other Sensor Error

CriticAXBSnsrErr

14

Yes

Hard or Soft

Sensor Error for EEV or HW

Alert-HotWtr

15

No

Auto

HW over limit or logic lockout. HW pump deactivated.

Fault-VarSpdPump

16

No

Auto

Alert is read from PWM feedback.

Not Used

17

No

Auto

IZ2 Com Fault. Autoreset upon condition removal.

Non-CritComErr

18

No

Auto

Any non-critical com error

Fault-CritComErr

19

No

Auto

Any critical com error. Auto reset upon condition removal

Alarm - Low Loop Pressure

21

No

Auto

Loop pressure is below 3 psi for more than 3 minutes

Alarm - Home Automation 1

23

No

Auto

Closed contact input is present on Dig 2 input - Text is configurable

Alarm - Home Automation 2

24

No

Auto

Closed contact input is present on Dig 3 input - Text is configurable

NOTES:
*All codes >11 use long flash for tens digit and short flash for the ones digit. 20, 30, 40, 50 etc. are skipped!
Alert’ is a noncritical sensor or function that has failed. Normal operation of the heat pump is maintained but service is desired at some point.

Fault LED (LED1, Red)

Red Fault LED

LED Flash

Code*

Lockout

Reset/

Remove

ABC Basic F

aults

Normal - No Faults

OFF

Fault - Input

1

No

Auto

Fault - High Pressure

2

Yes

Hard or Soft

Fault - Low Pressure

3

Yes

Hard or Soft

Fault - Freeze Detection FP2

4

Yes

Hard or Soft

Fault - Freeze Detection FP1

5

Yes

Hard or Soft

Fault - Condensate Overflow

7

Yes

Hard or Soft

Fault - Over/Under Voltage

8

No

Auto

Fault - FP1 & FP2 Sensor Error

11

Yes

Hard or Soft

NOTE: All codes >11 use long flash for tens digit and short flash for the ones
digit. 20, 30, 40, 50, etc. are skipped.

Aurora Base Fault Codes (ABC Only)

Aurora Advanced Fault Codes (ABC + AXB Expansion Board)

Controls - UPC DDC Control (optional) cont.