Blower performance data cont, Variable speed ecm motor, Envision – WaterFurnace Envision2 User Manual
Page 24: Compact installation manual, Single speed, Dual capacity
24
ENVISION
2
COMPACT INSTALLATION MANUAL
Blower Performance Data cont.
Variable Speed ECM Motor
Single Speed
Model
Max
ESP
Blower
Size
Motor
hp
Airfl ow DIP Switch Settings
1
2
3
4
5
6
7
8
9
10
11
12
015
0.50
9 x 7
1/2
300
400
500
600
700
L
M
H
018
0.50
9 x 7
1/2
300
400
500
600
700
800
L
M
H
024
0.50
9 x 7
1/2
400
500
600
700
800
900
1000
1100
1200
L
M
H
030
0.50
9 x 7
1/2
400
500
600
700
800
900
1000
1100
1200
L
M
H
036
0.50
11 x 10
1/2
650
750
850
1000
1100
1200
1300
1400
1500
L
M
H
036
w/1hp*
0.75
11 x 10
1
800
1000
1100
1300
1500
1600
1800
L
M
H
042
0.50
11 x 10
1/2
650
800
900
1050
1150
1250
1350
1450
1550
L
M
H
042
w/1hp*
0.75
11 x 10
1
800
900
1000
1200
1400
1600
1700
1850
2000
2200
2300
2400
L
M
H
048
0.50
11 x 10
1/2
650
800
900
1050
1150
1250
1350
1450
1550
L
M
H
048
w/1hp*
0.75
11 x 10
1
800
900
1000
1200
1400
1600
1700
1850
2000
2200
2300
2400
L
M
H
060
0.75
11 x 10
1
800
950
1100
1300
1500
1750
1950
2100
2300
L
M
H
070
0.75
11 x 10
1
800
950
1100
1300
1500
1750
1950
2100
2300
L
M
H
3/16/12
Dual Capacity
Model
Max
ESP
Blower
Size
Motor
hp
Air Flow DIP Switch Settings
1
2
3
4
5
6
7
8
9
10
11
12
026
0.50
9 x 7
1/2
400
500
600
700
800
900
1000
1100
1200
L
M
H
038
0.50
11 x 10
1/2
650
750
850
1000
1100
1200
1300
1400
1500
L
M
H
038
w/1hp*
0.75
11 x 10
1
800
1000
1100
1300
1500
1600
1800
L
M
H
049
0.50
11 x 10
1/2
650
800
900
1050
1150
1250
1350
1450
1550
L
M
H
049
w/1hp*
0.75
11 x 10
1
800
900
1000
1200
1400
1600
1700
1850
2000
2200
2300
2400
L
M
H
064
0.75
11 x 10
1
800
950
1100
1300
1500
1750
1950
2100
2300
L
M
H
072
0.75
11 x 10
1
800
950
1100
1300
1500
1750
1950
2100
2300
L
M
H
Factory settings are at recommended L-M-H DIP switch locations
M-H settings MUST be located within boldface cfm range
Lowest and Highest DIP switch settings are assumed to be L and H respectively
cfm is controlled within ±5% up to the maximum ESP
Max ESP includes allowance for wet coil and 1 in. MERV 4
3/16/12