Operating parameters, Operating limits, Operating parameters operating limits – WaterFurnace Versatec Base User Manual
Page 42
![background image](/manuals/743405/42/background.png)
42
VERSATEC BASE 50Hz SERIES INSTALLATION MANUAL
Operating Parameters
Operating Limits
Single Speed Models
SI
Entering
Water
Temp
°C
Water
Flow
L/s/kW
Cooling -- No Hot Water Generation
Suction
Pressure
kPa
Discharge
Pressure
kPa
Superheat Subcooling
Water
Temp
Rise
°C
Air Temp
Drop
°C DB
-1.1
0.09
793 - 862
1034 - 1172
11 - 19
6 - 9
9 - 12
9 - 13
0.19
724 - 827
896 - 1000
11 - 19
6 - 9
4 - 6
9 - 13
10
0.09
896 - 965
1482 - 1620
7 - 11
4 - 8
9 - 12
9 - 13
0.19
883 - 951
1310 - 1448
7 - 11
4 - 8
4 - 7
9 - 13
21.1
0.09
951 - 1020
1931 - 2137
6 - 9
6 - 9
8 - 12
9 - 13
0.19
938 - 1007
1724- 1931
6 - 9
4 - 8
4 - 7
9 - 13
32.2
0.09
1000 - 1069 2413 - 2620
5- 8
6 - 9
8 - 11
9 - 13
0.19
986 - 1055 2206 - 2413
5- 8
4 - 8
3 - 6
9 - 13
43.3
0.09
1000 - 1063 2896 - 3102
5- 8
6 - 9
8 - 11
9 - 13
0.19
986 - 1055 2792 - 2999
5- 8
4 - 8
3 - 6
9 - 13
Note: Cooling performance based on entering air temperatures of 80º F DB, 67º F WB.
Heating performance based on entering air temperature of 70º F DB.
Heating - No Hot Water Generation
Suction Pres-
sure kPa
Discharge
Pressure
kPa
Superheat
Subcooling
Water
Temp
Drop
°C
Air Temp
Rise
°C DB
503-586
1862- 2103
4 - 8
2 - 6
3 - 6
8 - 12
531 - 621
1931 - 2172
4 - 8
2 - 6
2 - 4
9 - 13
669 - 758
1999 - 2241
6 - 9
2 - 6
5 - 7
12 - 16
703 - 793
2068- 2310
6 - 9
2 - 6
4 - 6
13 - 17
896- 1000
2206 - 2448
7 - 11
2 - 6
6 - 8
17 - 20
931 - 1034
2241 - 2482
7 - 11
2 - 6
4 - 7
18 - 21
1034 - 1103
2413 - 2689
7 - 11
2 - 6
6 - 8
17 - 20
1069- 1038
2517 - 2792
7 - 11
2 - 6
4 - 7
18-21
12/5/14
Operating Limits
Cooling
Heating
(°C)
(°C)
Air Limits
Min. Ambient Air
7.2
7.2
Rated Ambient Air
26.7
21.1
Max. Ambient Air
37.8
29.4
Min. Entering Air
10.0
4.4
Rated Entering Air db/wb
27/19
20.0
Max. Entering Air db/wb
43/28.3
26.7
Water Limits
Min. Entering Water
-1.1
-6.7
Normal Entering Water
10-43.3
-1.1
Max. Entering Water
48.9
32.2
NOTE: Minimum/maximum limits are only for start-up conditions, and
are meant for bringing the space up to occupancy temperature. Units
are not designed to operate at the minimum/maximum conditions on
a regular basis. The operating limits are dependent upon three primary
factors: 1) water temperature, 2) return air temperature, and 3) ambient
temperature. When any of the factors are at the minimum or maximum
levels, the other two factors must be at the normal level for proper and
reliable unit operation.