Electrical data cont – WaterFurnace Versatec Base User Manual
Page 18
18
VERSATEC BASE 50Hz SERIES INSTALLATION MANUAL
Electrical Data cont.
Variable Speed ECM Motor
Model
Rated
Voltage
Voltage
Min/Max
Compressor
Blower
Motor
FLA
Total
Unit
FLA
Min
Circ
Amp
Max
Fuse/HACR
Breaker
MCC
RLA
LRA
005
220-240/50/1
198/264
13.1
5.5
24.0
4.0
9.5
10.9
15
006
220-240/50/1
198/264
12.6
6.7
46.0
4.0
10.7
12.4
15
380-420/50/3
342/462
6.0
2.9
30.0
4.1
7.0
7.7
10/15
007
220-240/50/1
198/264
14.0
8.0
46.0
4.0
12.0
14.0
20
380-420/50/3
342/462
6.4
3.2
30.0
4.1
7.3
8.1
10/15
009
220-240/50/1
198/264
17.7
9.9
67.0
4.0
13.9
16.4
25
380-420/50/3
342/462
7.1
3.8
34.0
4.1
7.9
8.9
10/15
010
380-420/50/3
342/462
7.7
4.2
34.0
4.1
8.3
9.4
10/15
012
220-240/50/1
198/264
25.5
13.8
81.0
4.0
17.8
21.3
30
380-420/50/3
342/462
8.0
5.6
44.0
4.1
9.7
11.1
15
015
380-420/50/3
342/462
12.0
6.7
55.0
6.9
13.6
15.3
20
017
380-420/50/3
342/462
11.5
7.1
55.0
6.9
14.0
15.8
20
HACR circuit breaker in USA only 12/5/14
Caution: When installing a unit with a Variable Speed ECM blower motor in 380-420/50/3 voltage, a neutral wire is
required to allow proper unit operation.