Blower performance data cont, Setting blower speed - variable speed ecm – WaterFurnace Versatec Base User Manual
Page 21
21
VERSATEC BASE SERIES 50Hz INSTALLATION MANUAL
Blower Performance Data cont.
Variable Speed ECM Motor
Model
Max
ESP (Pa)
Blower
Size
Motor
kW
Air Flow Dip Switch Settings
1
2
3
4
5
6
7
8
9
10
11
12
005
124.50
229 x 178
0.37
142
189
L
236
283
M
330
H
378
006
124.50
229 x 178
0.37
189
L
236
283
M
330
378
H
425
472
519
007
124.50
229 x 178
0.37
189
236
L
283
330
M
378
425
472
H
519
009
124.50
229 x 178
0.37
189
236
283
L
330
378
425
M
472
519
H
566
010
124.50
279 x 254
0.37
236
283
330
L
413
496
543
M
590
625
649
H
696
732
012
124.50
279 x 254
0.37
236
283
330
413
L
496
543
590
625
M
649
696
732
H
755
015
186.75
279 x 254
0.75
283
378
472
L
614
708
M
826
920
H
991
1038
1085
017
186.75
279 x 254
0.75
283
378
472
L
614
708
826
M
920
991
H
1038
1085
12/5/14
Factory settings are at recommended L-M-H DIP switch locations
CFM is controlled within ±5% up to the maximum ESP
M-H settings MUST be located within boldface CFM range
Max ESP includes allowance for wet coil and standard fi lter
Lowest and Highest DIP switch settings are assumed to be L and H respectively
Setting Blower Speed - Variable Speed ECM
Variable speed ECM blower motors have 12 selectable speeds and are factory set for optimum performance. When
applicable, the speed settings may also be adjusted through the Building Automation System (BAS).
CAUTION: Disconnect all power before performing this operation.