beautypg.com

Controls - upc ddc control (optional) cont – WaterFurnace Versatec Base User Manual

Page 37

background image

37

VERSATEC BASE SERIES 50Hz INSTALLATION MANUAL

1.

Accessory Relay2 – A second, configurable, accessory

relay on the AXB is provided that can be cycled with

the compressor 1 or 2 , blower, or the Dehumidifier (DH)

input. This is to complement the Accessory 1 Relay on

the ABC board.

2. Analog Out – A standard 0-10VDC analog output is

provided. This output can be used to drive modulat-

ing dampers etc.

3. Variable Speed Pump or Modulating Water Valve

- This input and output are provided to drive and

monitor a variable speed pump. The VS pump output

is a PWM signal to drive the variable speed pump. The

minimum and maximum level are set using the AID

Tool. 75% and 100% are the default settings respec-

tively. The VS data input allows a separate PWM signal

to return from the pump giving fault and performance

information. Fault received from the variable speed

pump will be displayed as E16. Modulating Water

Valve - This Variable speed PWM output is provided to

optionally drive a modulating water valve. Through ad-

vanced design a 0-10VDC valve can be driven directly

from the VS pump output. The minimum and maxi-

mum level are set in the same way as the VS pump

using the AID Tool. 75% and 100% are the default set-

tings respectively.

4. Loop Pump Slaving - This input and output are pro-

vided so that two units can be slaved together with a

common flow center. When either unit has a call for

loop pump, both unit’s loop pump relays and variable

speed pumps are energized. The flow center then can

simply be wired to either unit. The output from one

unit should be routed to the input of the other. If daisy

chained up to 16 heat pumps can be wired and slaved

together in this fashion.

Position

DIP 4

DIP 5

Description

1

ON

ON

Cycles with Fan or ECM (or G)

2

OFF

ON

Cycles with CC1 first stage of compressor

or compressor spd 1-12

3

ON

OFF

Cycles with CC2 second stage of

compressor or compressor spd 7-12

4

OFF

OFF

Cycles with DH input from ABC board

Aurora Advanced Control Configuration and Options

(Future Availability on Select Models/Configurations)

Controls - UPC DDC Control (optional) cont.