beautypg.com

On-line ups user manual, Appendix a: extended battery pack (ebp) user guide – SurgeX UPS-3000-OL User Manual

Page 31

background image

© SurgeX | Technical Support: 800-645-9721 | surgex.com

Page 30

On-Line UPS

User Manual

Models: UPS-1500-OL, UPS-2000-OL, UPS-3000-OL

SX-BDL-1500, SX-BDL-2000

15. Appendix A: Extended Battery Pack (EBP) User Guide

Estimated Run Time for UPS with Extended Battery Packs

MODEL

LOAD

RUNTIME FOR QTY OF EXTENDED BATTERY PACKS IN MIN.

VA

WATTS UPS

(1) EPB (2) EPB (3) EBP (4) EBP

(5) EBP

SX-BDL-1500

UPS-1500-OL

750

525

18

68

124

184

248

315

1500

1050

9

32

60

90

120

152

SX-BDL-2000

UPS-2000-OL

1000

700

29

109

200

298

402

510

2000

1400

14

52

97

144

194

247

UPS-3000-OL

1500

1050

18

67

123

184

248

315

3000

2100

9

32

60

89

120

152

CAUTION: It is very critical to connect the correct voltage EBP with the UPS intended.

UPS-BPX-1500 is for SX-BDL-1500/UPS-1500-OL

UPS-BPX-2000 is for SX-BDL-2000/UPS-2000-OL/UPS-3000-OL

Connecting the incorrect battery pack to the UPS may result in damage to the UPS and/or battery pack

will void the warranty.

All EBPs have a different DC voltage configuration intended only for the UPS’s listed above. Please do

not mix BPX’s and make sure you only connect the EBP to like EBPs or UPS indicated above. DC

voltages are marked on both the UPS and the EBP – MAKE SURE THEY MATCH.

CAUTION LABEL ON EBP CABLE CONNECTORS –

PLEASE CHECK VOLTAGES CAREFULLY

This manual is related to the following products: