The RS-232 communication port provides the following functions:

1) Monitoring charger status

2) Monitoring battery status and condition

3) Monitoring inverter status

4) Monitoring UPS status

5) Monitoring the utility status

6) Providing the power switch function for computer to turn on/off the utility on schedule

for power saving

7) Adjustable Transfer voltage

The UPS data is provided at 2400 bps baud rate and made up of 8-bit, 1 stop-bit and no

parity bit. All information is encoded in ASCII format.

HARDWARE:

BAUD RATE----------------2400 bps

DATA LENGTH------------8 bits

STOP BIT--------------------1 bit

PARITY----------------------NONE

CABLING:

Standard D-sub 9 cable (UPS side: male, PC side: female)


8-2 Dry Contact

Pin1 : The pin is normally open. When battery low, pin1 and pin5 are connected

via photo coupler.

Pin3 : The UPS will shut down when a high level (5~12V) sustained for at least

3.8 seconds is applied.

Pin5 : Signal ground.

Pin6,7 : Reserved.

Pin8 : The pin is normally open. When utility fails, pin8 and pin5 are connected

via photo coupler.

CABLING: The user must use the special cable. The connection is described as follows:

PC

(female)

UPS

(male)

Pin1------------------Pin1 (battery Low)

Pin3------------------Pin5 (GND)

Pin4------------------Pin3 (Shutdown)

Pin7------------------Pin6

Pin7------------------Pin7

Pin8------------------Pin8 (AC Fail)

The communication port at the back of the UPS may be connected to a computer. This

port allows the computer to monitor the UPS and control the operation of the UPS in

some cases.