8. COMMUNICATION INTERFACE
The UPS provides RS-232 and Dry contact protocols in one D-sub 9 connector. Using
proper UPS management software and cable, the UPS can be managed over
LAN/intranet/internet environment. The pin assignment of the D-sub 9 connector is
defined as follows:
ASSIGNMENT DESCRIPTION
PIN
RS-232 Dry
Contact
1
Low
battery(Open
collector)
2
UPS TxD(typical RS-232 level)
3
UPS RxD(typical RS-232 level)
Remote shutdown(5~12V)
4
Reserved for PNP
5 GND GND
6
Reserved for PNP
Reserved
7
Reserved for PNP
Reserved
8
Utility Fail(Open collector)
9
Fig 8-1 Pin Assignment Fig 8-2 Open Collector Circuit
Maximum voltage and current on pin 1,8 is 30VDC, 10mA.
8-1 RS-232
Pin2
: PC receives line RS-232 data from UPS.
Pin3 : PC transmits line RS-232 data to UPS.
Pin5
: Signal ground.
Pin4,6,7 : Reversed for plug and play function.