beautypg.com

Installation, 5 water systems - domestic hot water 5.4 general, 5 water pressure – Glow-worm Flexicom cx User Manual

Page 16: 6 ‘hard’ water areas, 7 domestic water flow rate, 9 bypass, 10 safety valve

background image

0020107232_03 - 12/14 - Glow-worm

INSTALLATION

- 16 -

5 Water systems - Domestic Hot Water

5.4 General

All domestic hot water circuits, connections, fittings must be

in accordance with the relevant standards and water supply

regulations.

For GB: Guidance G17 to G24 and recommendation R17 to

R24 of the Water Regulations Guide

(for Scotland, the Water

Byelaws 2000, Scotland)

.

For IE: The current edition of I.S.813 “Domestic Gas

Installations”.

5.5 Water Pressure

The minimum working pressure to obtain the maximum

domestic flow is:-

24cx 1.0bar

30cx 1.0bar

35cx 1.0bar

The maximum working pressure of the domestic hot water

circuit is 10 bar. If the cold water supply pressure exceeds this,

then a pressure-reducing valve must be fitted in the supply to

the boiler.

5.6 ‘Hard’ Water Areas

The temperatures within the heat exchanger are limited by the

boiler control system to minimise scale formation within the hot

water pipework. However, in areas where the water is ‘hard’ (i.e.

more than 200mg/litre), it is recommended that the hot water

setting is reduced and that a scale reducer is fitted, refer to the

manufacturer’s instructions or consult the local water company

for additional advice.

5.7 Domestic Water Flow Rate

The water flow rate is restricted to a maximum 9.4 l/min for

24cx, 11.7 l/min for 30cx and 13.0l/min for 35cx by a restrictor

factory fitted within the boiler.

15725

Diagram 5.3

5 Water Systems - Sealed Central Heating

system
5.8 Flow Rate

If it is necessary to alter the flow rate, the system can be fitted

with a lockable balancing valve in the main flow or return pipes

shown as valve “A” in diagram 5.3. The flow rate through the

boiler must not be allowed to fall below that given in section 1 -

Specification Table.

5.9 Bypass

The boiler is fitted with an automatic bypass.

Diagram 5.2 shows the pump head remaining for the heating

system depending on the bypass setting and the speed setting

of the pump, see section 11 Commisioning.

Ensure that under no circumstances does the flow rate drop

below the figure specified, refer to section 1 - Specification

Table and section 11.9.

5.10 Safety Valve

The safety valve is an integral part of the boiler and it cannot

be adjusted.

The pipe from the safety discharge valve must

not discharge above an entrance, window or any type of public

access area.