6 servicing – Glow-worm Clearly Heat Recovery User Manual
Page 22

22
NOTE: Replace the filters at least once a year or
after maximum 2000 operating hours. If the filters are heavily
soiled, they should be replaced at shorter intervals.
A
competent person approved at the time by the Health and
Safety Executive in the area of the air pollution control, should
carry out regular inspections. The first inpection should be
performed 3 months after commissioning.
To avoid damaging the unit, the following maintenance work
must be carried out by a
competent person approved at the
time by the Health and Safety Executive.
The functional operation of the ventilation unit requires it to be
serviced once per year, this includes the following:
•
Check the general condition of the unit
•
Remove any dirt and soiling at the unit.
•
Clean or replace soiled filters.
•
Clean the condensate outlet and check if the duct is free
•
Clean soiled fan.
•
Check the function of the unit, the remote control and the
bypass.
6.1 Removing and Cleaning the Filter of the
Ventilation Unit
Open the unit and remove the filters then the front panel as
shown in diagram 6.1.
If the filters are not heavily soiled, you may clean them with a
normal vacuum cleaner.
If this is not enough, the filters must be replaced.
Cleaning the filters with water or other liquids is expressly
prohibited.
6 Servicing
Description
Filter
class
Ordering number
Filter Atmosorb
G3
0020064722
Filter Atmosorb Bypass
G3
0020064723
High efficiency filter Atmosorb
F6
0020064720
High efficiency filter Atmosorb Bypass F6
0020064721
a
a
c
b
e
d
Diagram 6.1
14885