19

5 Commissioning

Action

Display Meaning

press

mode

button

for 10

secs

AIR1

Set volume flow night

1st stage
Atmosorb HRD

275

350

Default setting m

3

/h

80

105

Min m

3

/h

50

70

Max m

3

/h

AIR2

AIR2

Set volume flow for the

non-programmed periods.

press

prog

button

AIR2

Set volume flow day

2nd stage
Atmosorb HRD

275

350

Default setting m

3

/h

165

210

Min m

3

/h

AIR1

AIR1

Max m

3

/h

HIGH

HIGH

Set volume flow for the programmed periods.

Action

Display Meaning

press

prog

button

HIGH

Set volume flow, 3rd stage
Atmosorb HRD

275

350

Default setting m

3

/h

275

350

Min m

3

/h

AIR2

AIR2

Max m

3

/h

325

400

Must value of the volume flow after the activati-

on of the special function "Advance Mode" with

the key F.

press

prog

button

AIR4

Set volume flow holiday
Atmosorb HRD

275

350

Default setting m

3

/h

60

75

Min m

3

/h

50

70

Max m

3

/h

AIR2

AIR2

Set volume flow after activation of the special

function "holidays" with the F button, additio-

nally in "OFF" mode.

press

prog

button

AIR5

Min. volume flow with activated

bypass

Atmosorb HRD

275

350

Default setting m

3

/h

110

140

Min m

3

/h

AIR1

AIR1

Max m

3

/h

HIGH HIGH

Minimum volume flow when the connected by-

pass switches to summer mode (without heat

recovery).

press

prog

button

STOV

Protective switching against

negative pressure
Atmosorb HRD

275

350

Factory setting

OFF

OFF

ON = If one fan fails, the other fan is also de-

activated.

This protective switching prevents negative

pressure as a result of only disconnecting the

supply fan. If the protective switching against

the low pressure is activated, both fans are

switched off by the frost protection function.

press

prog

button

FILT

Days till the next filter replacement
Atmosorb HRD

275

350

Default setting/days

180

180

Min. days

30

30

Max. days

180

180

Adjusted in 30 day steps to which the indica-

tion "FILT" is shown on the remote control dis-

play. (Alarm output is closed)

press

prog

button

POL1

POL2

No function

Please refer to diagram 5.1 for control panel buttons and layout:

Table 5.1 Installer level

Table 5.1 Installer level (continued)