background image

Catalytic S/T

ENMET Corporation

3

2.0 Catalytic Combustible Gas Sensor/Transmitter Installation

2.0 Catalytic Combustible Gas Sensor/Transmitter Installation

The ENMET catalytic combustible gas sensor/transmitter (S/T) is a three or four wire 4-20 mA S/T for the detection
of combustible gas. The S/T is meant to be used in conjunction with an appropriate power supply and controller. The
S/T is in an enclosure rated for use in a Class I, Div. 1, Groups B, C, D, classified area.

2.1 Installation

C

AUTION

:

Area must be declassified during installation.

2.1.1 Mounting

Mount the enclosure, using the two mounting holes provided see figure 1. Pay particular attention to the source and
density of the gas being detected when choosing the location.

C

AUTION

:

Before connecting S/T to controller remove the power source to controller. Failure to do so may cause
damage to sensitive components.

Figure 1: Mounting Dimensions of Catalytic Combustible Gas Sensor/Transmitter

Sensor

Mounting Holes
2 places, 0.313

″″

Sensor/Transmitter
Enclosure Side View

Sensor/Transmitter
Enclosure Top View

Sensor

T

OP

V

IEW

S

IDE

V

IEW

Conduit fitting
Typically: ½

″″ NPT female

Approx.

12

5