ENMET EX-6100 Series User Manual
Page 9
EX-6100
ENMET Corporation
6
3.5 Following Completion of the Installation:
a)
Replace the top display board using the locating pins on the underside of the board to ensure that it makes connection
with the remainder of the electronics - see Figure 8.
b)
Ensure that the front cover has not been contaminated with dirt - paying particular attention to the thread. Replace the
cover by rotating it several times clockwise until it reaches its limit then secure using the set screw – do not over
tighten.
Figure 8: Replacing the Display Board
3.6 Applying power
Caution:
The cover must be in place before applying power
Once the installation is complete and the covers are secure then power can be applied. The power source should be between 8
and 24 volts dc.
When power is first applied to the
EX-6100
, an initialization procedure is performed as follows:
All segments on the LCD are shown
8.8:8.8
The software version is displayed
1.3.0
The manufacturer code is displayed
SSCL
The sensor type is displayed
P
Warm up count down
30
The detected gas level present is displayed and the
EX-6100
becomes operational.
3.7 Indicators
Three LED indicators are visible from the front panel of the instrument. These are:
Color
Identity
Operation
Red
Alarm
Illuminates when either alarm level has been reached.
Green
Power
Always ON when power is connected.
Yellow
Key press
Illuminates when the magnetic switches are operated.