Beckett NX

1.

Room temperature drops, thermostat calls for heat.

2.

Pre-purge begins, lasting 5 to 15 seconds.

3.

Oil solenoid and BVS are energized

4.

Oil Solenoid opens allowing oil to reach Burner

Electrodes. Burner ignition begins.

5.

If vent is clear, pressure switch closes, Cad cell detects

light from combustion the primary control safety circuit

disconnects allowing combustion to continue. BVS is

energized.

6.

After 15 to 45 seconds (depending on primary control

characteristics), electric spark across electrode tips

stops, combustion continues.

7.

Boiler continues operation and reaches “steady state”,

point at which system temperature stabilizes.

8.

Room temperature rises, thermostat is satisfi ed,

heating contacts open.

9.

Oil solenoid valve closes, combustion stops, burner

motor remains on to complete Post Purge Cycle.

Post Purge time can be 0 to 8 minutes depending on

settings. Factory default is 2 minutes. Timing can be

changed using Beckett 5206 Genisys display.

10.

Boiler remains idle until next call for heat.

Riello 40BF
1.

Room temperature drops, thermostat calls for heat.

2.

Pre-purge begins, lasting 5 to 15 seconds. BVS is

energized.

3.

If fl ue is clear, pressure switch allows ignition sequence

to continue.

4.

Oil Solenoid opens allowing oil to reach burner

electrodes. Burner ignition begins.

5.

Cad cell detects light from combustion, disconnects

primary control safety circuit, allowing combustion to

continue.

6.

After 15 to 45 seconds (depending on primary control

characteristics), electric spark across electrode tips

stops, combustion continues.

7.

Boiler continues to operate and reaches “steady state”,

the point at which the system temperature stabilizes.

8.

Room temperature rises, thermostat is satisfi ed,

heating contacts open.

9.

Oil solenoid valve closes, combustion stops, burner

motor remains on to complete post purge cycle. Post

purge time can be 10 seconds to 5 minutes depending

on settings. Factory default is 45 seconds. Timing can

be changed by rotating dial on Riello burner fan-off

timer control board.

10.

Boiler remains idle until next call for heat.