Figure 4 - Inside View of Vent Terminal

Figure 5 - Vent Terminal Riser

Vent Terminal Location

See table 1 for equipment certifi ed for use with this

appliance.
Select location of wall penetration that conforms to code for

exterior location:

1.

As close to appliance as possible,

2.

Maintains clearance to combustibles,

3.

Maintains minimum 1/4 inch per foot slope back to

appliance.

4.

Install vent terminal in wall having minimum thickness

of 5”, and maximum thickness of 10”.

Vent Terminal Installation

• Cut a 6-1/2” diameter hole through the wall.
• Remove Intake Air Sleeve from Terminal.
• Insert Terminal through the wall from outside, secure

with 4 screws to the wall, and seal to wall with

weatherproof sealant.

• From inside the building, re-attach Intake Air Sleeve and

secure inner sleeve to outer sleeve with 2 screws.

• Use 4 screws to secure Sleeve to wall. See Figure 4.
• Insure Intake Air Connector is located for easy attach-

ment and complies with code.

Vent Terminal Riser Kit

Kit is designed to increase height of vent terminal by

approximately 3 feet.
Ideal where excessive snow build up could occur or where

more fl exibility is required to maintain minimum clearances

at grade. See fi gure 5.

VENT TERMINAL INSTALLATION