NX Burner With Blocked Vent Safety (BVS) Operation

External Action

Appliance Response

Power applied to burner control

Internal safety check conducted. If no light or fl ame is detected and all internal conditions are correct,

control enters idle mode.

Thermostat Calls For Heat

Call for heat is satisfi ed.

Reset button pushed two times

without device completing a call for

heat.

GeniSys 7505 Reset Button Operations
Pushing the reset button in the current state will cause the following conditions:

If the burner state is:

Pushing the reset button < 1 second

Pushing the reset button > 1 second

Push, hold reset button >15

seconds

Lockout

Reset from Soft Lockout

Reset from Restricted (Hard)

Lockout

Valve On Delay, Trial For

Ignition, Ignition Carryover

Pump Prime

Disable the Burner. Any time the

burner is running, press and hold the

reset button to disable the burner. The

burner will remain off as long as the

button is held.

Enables pump priming: After the

reset button has been held for 15

seconds the button can then be

clicked during the next ignition

sequence to enter pump prime

mode.

Run (igniter is shut off)

Yellow light fl ashes to indicate cad cell

resistance.

Motor-Off Delay, Standby

No action

Pump Prime

No action

Exit pump prime mode and return to standby.

Status Lights

Light Color

On Continuously

Flashing

Red

Restricted (Hard) Lockout

Soft Lockout

Green

Flame Sense during normal operation.

May be stray light during standby.

Recycle

Yellow

Control is in Pump Prime mode OR

reset button is currently held for >15

seconds.

Cad cell resistance.

OPERATION AND TROUBLESHOOTING